Operating Instructions
Safety Relay with IO-Link ESM-CB
26
(Translation of the original operating instructions) 2522722-01-05/19
14.4. Acyclical data (device data and events)
14.4.1. Writing and reading services
Important!
The manufacturer’s code for EUCHNER is 0x01.
Index 100 – reading service: size of the input/output data areas
Index
dec (hex)
Subindex
dec (hex)
No.
Type
Description
100 (64)
0 (0)
1 (1)
1
UInt8
Manufacturer’s code of safety switch 1
2
UInt8
Input process-data size of safety switch 1
3
UInt8
Output process-data size of safety switch 1
2 (2)
4
UInt8
Manufacturer’s code of safety switch 2
5
UInt8
Input process-data size of safety switch 2
6
UInt8
Output process-data size of safety switch 2
…
…
UInt8
…
31 (1F)
91
UInt8
Number of safety switches
Index 101 – reading service: manufacturer’s codes of the devices
Index
dec (hex)
Subindex
dec (hex)
No.
Type
Description
101 (65)
0 (0)
1 (1)
1
UInt8
Manufacturer’s code of safety switch 1
2 (2)
2
UInt8
Manufacturer’s code of safety switch 2
…
…
UInt8
…
30 (1E)
30
UInt8
Manufacturer’s code of safety switch 30
31 (1F)
31
UInt8
Number of safety switches
Index 102 – reading service: size of the input data area
Index
dec (hex)
Subindex
dec (hex)
No.
Type
Description
102 (66)
0 (0)
1 (1)
1
UInt8
Input process-data size of safety switch 1
2 (2)
2
UInt8
Input process-data size of safety switch 2
…
…
UInt8
…
30 (1E)
30
UInt8
Input process-data size of safety switch 30
31 (1F)
31
UInt8
Number of safety switches
Index 103 – reading service: size of the output data area
Index
dec (hex)
Subindex
dec (hex)
No.
Type
Description
103 (67)
0 (0)
1 (1)
1
UInt8
Output process-data size of safety switch 1
2 (2)
2
UInt8
Output process-data size of safety switch 2
…
…
UInt8
…
30 (1E)
30
UInt8
Output process-data size of safety switch 30
31 (1F)
31
UInt8
Number of safety switches