Emergency Stop Safety Relay ESM-BA2.. 

V1.1.0 

Note: 

The items listed under “Electrical connection” must be observed during commissioning

.

 

Commissioning 
Procedure 

1. Wiring emergency stop circuit: 

Wire  the  emergency  stop  circuit  according  to  the  required 
Performance Level determined (see Fig. 1 to Fig. 5). 

2. Wiring start circuit: 

Wire the start circuit according to Fig. 6 or Fig. 7 to set the 
starting behavior. 

Warning: 

If  “Automatic  start”  is  set,  bear  in  mind  that  the  safety 
contacts  will  switch  immediately  after  the  power  supply  is 
connected.  If  “Monitored  manual  start”  is  set,  the  start 
button must be opened after wiring. 

3. Wiring feedback loop: 

If  your  application  provides  for  external  contactors  or  ex-
pansion modules, connect them to the device according to 
Fig.8 or Fig. 9. 

4. Wiring power supply: 

Connect the power supply to terminals A1 and A2 (Fig. 10). 

Warning:

 Wiring only in de-energized state. 

5. Starting the device: 

Switch on the operating voltage. 

Warning: 

If  the  “Automatic  start”  starting  behavior  is  set,  the  safety 
contacts will close immediately. 

If the “Monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 

LEDs 

K1

 and 

K2

 are lit. 

6. Triggering safety function: 

Open  the  emergency  stop  circuit  by  actuating  the  connec-
ted safety switch. The safety contacts open immediately. 

7. Reactivation: 

Close  the  emergency  stop  circuit.  If  “Automatic  start”  is 
selected, the safety contacts will close immediately. 

If the “Monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 

Fig. 6: 

Monitored manual start. 
It is monitored that the start 
button was opened before the 
emergency stop button closes.  
(Prerequisite:  
operating voltage must not be 
interrupted.) 

Fig. 7: 

Automatic start. 
Max perm. delay during 
closing of the safety switches 
on S12 and S13: 
S12 before S13: 300 ms 
S13 before S12: any 

Warning: 

Safety contacts switch 
immediately when the 
power supply is connected. 

Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as 
shown in Fig. 1 to Fig. 11.  

Applications 

Fig. 3: 

Single-channel emergency stop 
circuit with earth fault monito-
ring.  
(category 1, up to PL c) 

Fig. 2: 

Two-channel emergency stop 
circuit with earth fault monitoring.  
(category 3, up to PL d) 

Fig. 1: 

Two-channel emergency stop 
circuit with short circuit and earth 
fault monitoring.  
(category 4, up to PL e) 

Fig. 4: 

Two-channel sliding guard 
monitoring with short circuit and 
earth fault monitoring.  
(category 4, up to PL e) 

Emergency Stop 
Circuit 

Starting Behavior 

Fig. 8: 

Feedback loop for monitored manual 
start: 
The feedback loop monitors contactors 
or the expansion modules . 

Feedback Loop 

Fig. 9: 

Feedback loop for automatic start: 
The feedback loop monitors contac-
tors or the expansion modules . 

Power supply  
and  
Safety contacts 

Fig. 10: 

Power supply A1 and A2. 
 
(Power supply according to techn. 
data ) 

Fig. 11: 

Connecting load to safety contacts. 
 
(Figure shows example.  
Voltage „+V“ according to techn. 
data) 

Warning only for 24V-version:  

In  order  to  activate  earth  fault  monitoring,  the  PE  must  be 
connected only to the power supply unit in accordance with 
EN60204-1. 

 

Corresponded to the application, the starting circuit have to 
be wired according to Fig. 6 or Fig. 7.

 

Fig. 5: 

Two-channel emergency stop 
with pnp-outputs/OSSD-outputs 

with

 short circuit monitoring. 

(category 4, up to PL e) 

Summary of Contents for ESM-BA2 Series

Page 1: ...ith electrical isolation from the mains must be connected External fusing of the safety contacts must be provided A maximum length of the control lines of 1000 meters with a line cross section of 0 75 mm2 must not be excee ded The line cross section must not exceed 2 5 mm2 If the device does not function after commissioning it must be returned to the manufacturer unopened Ope ning the device will ...

Page 2: ...et close the start button to close the safety contacts Fig 6 Monitored manual start It is monitored that the start button was opened before the emergency stop button closes Prerequisite operating voltage must not be interrupted Fig 7 Automatic start Max perm delay during closing of the safety switches on S12 and S13 S12 before S13 300 ms S13 before S12 any Warning Safety contacts switch immediatel...

Page 3: ...on 2 DIN VDE 0110 1 Overvoltage category 3 DIN VDE 0110 1 Weight approx 230 g Mounting DIN rail according to EN 60715 TH35 Note Additional data can be requested from the manufacturer for applications that deviate from these conditions Safety Characteristics According to EN ISO 13849 1 The device is certified according to EN ISO 13849 1 up to a Performance Level of PL e Device cannot be switched on...

Page 4: ...75 33 16 www euchner de info euchner de Emergency Stop Safety Relay ESM BA2 V1 1 0 Dimension Drawing Subject to technical modifications no responsibility is accepted for the accuracy of this information EUCHNER GmbH Co KG 090071 06 02 16 Translation of the Original Operating Instructions Fixed Terminals Plug In Terminals ...

Reviews: