![EUCHNER CTM-CBI-BP Operating Instructions Manual Download Page 12](http://html.mh-extra.com/html/euchner/ctm-cbi-bp/ctm-cbi-bp_operating-instructions-manual_2434847012.webp)
Operating Instructions
Transponder-Coded Safety Switch CTM-CBI-BP
12
(Translation of the original operating instructions) 2541786-01-10/20
7. Manual release
Important!
Ì
All release functions latch when the device is electrically isolated.
Ì
Guard locking remains released when the release function is reset.
Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test
should be performed after release.
More information on this topic can be found in the standard EN ISO 14119:2013, section 5.7.5.1. The device can feature
the following release functions:
7.1.
Auxiliary release
In the event of malfunctions, the guard locking can be released with the auxiliary release irre-
spective of the state of the solenoid.
Ì
When release monitoring is active, the system enters into a latching fault when the auxiliary
release is actuated. See
Signal sequence incorrect
status (DIA red,
Lock flashes 1 time).
Ì
The safety outputs are switched off when the auxiliary release is actuated.
Guard lock monitoring output/bit OL is switched off; door position monitoring output/bit OD
can assume an undefined state. Open the guard and close it again after resetting the auxiliary
release. The device will then operate normally again.
7.1.1. Actuating auxiliary release
1. Remove seal label or make a hole.
2. Using a screwdriver, turn the auxiliary release to in the direction of the arrow.
¨
Guard locking is released.
Important!
Ì
The actuator must not be under tensile stress during manual release.
Ì
Reset the auxiliary release and cover it with a new seal label after use.
Ì
Loss of the release function due to mounting errors or damage during mounting.
Ì
Check the release function every time after mounting.
Ì
After manual release, the solenoid must be energized briefly to re-establish the defined state.
Ì
Please observe the notes on any enclosed data sheets.
Ì
The auxiliary release must be reset at the control system level, e.g. by means of a plausibili-
ty check (status of the safety outputs does not match the guard locking control signal). See
EN ISO 14119:2013, sec. 5.7.5.4.
Ì
The auxiliary release is not a safety function.
Ì
The machine manufacturer must select and use a suitable release (escape release, emergency
release, etc.) for a specific application. A hazard assessment is required for this purpose. It may
be necessary to take specifications from a product standard into account.
Ì
The correct function must be checked at regular intervals.
Ì
Loss of the release function due to mounting errors or damage during mounting. Check the re-
lease function every time after mounting.
Ì
Please observe the notes on any enclosed data sheets.
Auxiliary
release