Operating Instructions

Key Adapter CKS-A-L1B-SC

Correct use

Series CKS key adapters are operated in combi-

nation with an evaluation unit in the system family 

CES-AZ-.ES-… or CES-FD-…
This safety component allows dangerous machine 

movements to be undertaken as long as a valid key 

is inserted. A stop command is triggered if the key 

is removed during the dangerous machine function.
Before use, a risk assessment must be performed 

on the machine, e.g. in accordance with:

 

f

EN ISO 13849-1

 

f

EN ISO 12100

 

f

IEC 62061

Correct use includes observing the relevant require-

ments for installation and operation, e.g.

 

f

EN ISO 13849-1

 

f

EN 60204-1

The key adapter must be used only in conjunction 

with the designated CKS keys from EUCHNER. On 

the use of different keys, EUCHNER provides no 

warranty for safe function.

Important:

 

f

The user is responsible for the proper integration 

of the device into a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. in accordance with EN ISO 13849-2.

 

f

Correct use requires observing the permissible 

operating parameters (see section Technical 

data).

 

f

If a product data sheet is included with the prod-

uct, the information on the data sheet applies 

in case of discrepancies with the operating 

instructions.

Exclusion of liability and warranty

In case of failure to comply with the conditions for 

correct use stated above, or if the safety instruc-

tions are not followed, or if any servicing is not 

performed as required, liability will be excluded and 

the warranty void.

Safety precautions

Safety components fulfill personal protection func-

tions. Incorrect installation or tampering can lead to 

fatal injuries to personnel.
Check the safe function of the safety guard par-

ticularly

 

f

after any setup work

 

f

after the replacement of a system component

 

f

after an extended period without use

 

f

after every fault

Independent of these checks, the safe function of the 

safety guard should be checked at suitable intervals 

as part of the maintenance schedule.

 WARNING

Danger to life due to improper installation or due 

to bypassing (tampering). Safety components 

perform a personal protection function.

 

f

The switching operation may be triggered only 

by keys specially designated for this purpose.

 

f

The key must be completely pulled out of the 

key adapter in order to switch the safety circuit 

off safely.

 

f

Mounting, electrical connection and setup only 

by authorized personnel possessing the following 

knowledge:

 

specialist knowledge in handling safety com-

ponents 

 

knowledge about the applicable EMC regulations

 

knowledge about the applicable regulations on 

occupational safety and accident prevention.

 

f

Use as a lockout mechanism only in combination 

with unicode evaluation units.

Function

The key adapter CKS can be used as a lockout 

mechanism, for example. As soon as the key is in 

the key adapter, the LED on the key adapter illumi-

nates white and data transmission to the evaluation 

unit begins. The read code is compared with the 

taught-in code in the evaluation unit. Each delivered 

key possesses a unique electronic coding and so 

is a unique element in the system used. 
The code of a key cannot be reprogrammed. 
When the key is removed from the key adapter, 

the white LED goes out, the outputs of the CES 

evaluation unit are switched off and the machine 

cannot be started. 
In the event of a fault in the key adapter, the outputs 

of the CES evaluation units will be switched off. 

Mounting

NOTICE

 

f

The key adapter must not be opened.

 

f

To achieve the degree of protection IP65/IP67, 

it is necessary to install the key adapter in a 

clean, flat metal plate at least 2 mm thick and 

to tighten the screws with a tightening torque of 

0.25 … 0.35 Nm.

 

f

The device may be damaged if the tightening 

torque applied exceeds 0.35 Nm.

 

f

A suitable strain relief must be provided for the 

connection cables in order to avoid damage to 

the connection sockets or malfunctions.

The key adapter is intended for mounting in control 

panels with a cut-out measuring 33 mm x 68 mm 

according to DIN IEC 61554:2002-08. The device 

is fastened using screw clamp elements from the 

rear side of the panel.
1.  Insert the key adapter, with seal already bond-

ed in place, into the mounting cut-out from the 

front.

2.  Insert screw clamp elements in the housing of 

the key adapter from the side up to the stop 

and tighten with 0.25 …0.35 Nm.

3.  After mounting, again check the key adapter 

for firm seating and correct sealing of the front 

panel.

Protection against environmental 

effects

Remove dirt from the key and the key adapter 

using a soft cloth and solvent-free, non-abrasive 

cleaning agents. 
Cover the key adapter and the key during painting 

work.

Electrical connection

 WARNING

 

f

The key adapter CKS must be used only with 

a suitable EUCHNER connection cable. The 

connection cable contains two screened cores 

to transmit the signals from the key adapter to 

the evaluation unit.

 

f

All the electrical connections must either be 

isolated from the mains supply by a safety 

transformer according to IEC EN 61558-2-6 with 

limited output voltage in the event of a fault, or 

by other equivalent isolation measures.

 

f

For terminal assignment, see Figure 1.

 

f

For detailed information, see the operating instruc-

tions for the evaluation unit used.

Setup and functional check

Observe the information in the operating instructions 

for the respective evaluation unit during setup.

 WARNING

Danger of fatal injuries as a result of faults in 

installation and functional check.

 

f

Before carrying out the functional check, make 

sure that there are no persons in the danger area.

 

f

Observe the valid accident prevention regula-

tions.

Teach-in function for the key
See manual of the related evaluation unit.
Electrical function test
After installation and any fault, the safety function 

must be fully checked. Proceed as follows:
1.  Switch on operating voltage.

 

f

The machine must not start automatically.

 

f

The CES evaluation unit carries out a self-test.

2.  Insert key.

 

f

The LED illuminates white.

3.  Enable operation in the control system.
4.  Remove key.

 

f

The machine must switch off and it must not be 

possible to start it as long as a key is not inserted.

 

f

The LED goes out.

Repeat steps 2 … 4 for each key adapter.

Inspection and service

 WARNING

Loss of the safety function because of damage 

to the system.

 

f

In case of damage, the entire device must be 

replaced. 

 

f

Only accessories or spare parts that can be 

ordered from EUCHNER may be replaced.

Regular inspection of the following is necessary to 

ensure trouble-free long-term operation:

 

f

Check the switching function

 

f

Check the secure fastening of the devices and 

the connections

 

f

Check for soiling.

No servicing is required. Repairs to the device are 

only allowed to be made by the manufacturer.
Notice:
The year of manufacture can be seen in the lower 

right corner of the type label.

Exclusion of liability and warranty

In case of failure to comply with the conditions for 

correct use stated above, or if the safety instruc-

tions are not followed, or if any servicing is not 

performed as required, liability will be excluded and 

the warranty void.

Summary of Contents for CKS-A-L1B-SC

Page 1: ...f f Um die Schutzart IP65 IP67 zu erreichen ist es erforderlich die Schlüsselaufnahme in eine saube re ebene Metallplatte mit mindestens 2 mm Dicke einzubauen und die Schrauben mit einem Anzugs drehmoment von 0 25 0 35 Nm anzuziehen f f Bei einem Anzugsdrehmoment von über 0 35 Nm kann das Gerät beschädigt werden f f Um Beschädigungen an den Anschlussbuchsen oder Funktionsstörungen zu vermeiden mus...

Page 2: ...A 6 GF30 Masse 0 13 kg Schutzart IP65 IP67 in eingebautem Zustand Einbaulage frontseitig Montage Ausschnitt nach DIN IEC 61554 2002 08 33 x 68 mm Umgebungstemperatur 20 70 C Ansprechbereich 1 Gesicherter Ausschaltabstand sar Gesicherter Schaltabstand sao Schalthysterese 30 mm 2 mm 1 mm Anschluss an Auswertegerät Steckverbinder M8 Stiftdose 3 polig Max Leitungslänge in Kombination mit Auswertegerät...

Page 3: ...f f The key adapter must not be opened f f To achieve the degree of protection IP65 IP67 it is necessary to install the key adapter in a clean flat metal plate at least 2 mm thick and to tighten the screws with a tightening torque of 0 25 0 35 Nm f f The device may be damaged if the tightening torque applied exceeds 0 35 Nm f f A suitable strain relief must be provided for the connection cables in...

Page 4: ...terial Plastic PA 6 GF30 Weight 0 13 kg Degree of protection IP65 IP67 in mounted condition Installation position On the front panel Mounting cut out acc to DIN IEC 61554 2002 08 33 x 68 mm Ambient temperature 20 70 C Operating distance 1 Assured switch off dist sar Assured switch on dist sao Switching hysteresis 30 mm 2 mm 1 mm Connection to evaluation unit Plug connector M8 male socket 3 pin Max...

Reviews: