9.6. Connector assignment of safety switch CES-I-AR
Coding lug
1
7
6
5
4
3
2
8
8
2
7
6
1
3
4
5
UB
0V
FI1A
FI1B
FO1A
FO1B
OD
RST
View of connection side on the safety switch
Figure 2:
Connector assignment of safety switch CES-I-AR
Pin
Designation
Description
Wire color
1
FI1B
Enable input for channel 2
white
2
UB
Power supply, DC 24 V
brown
3
FO1A
Safety output, channel 1
green
4
FO1B
Safety output, channel 2
yellow
5
OD
Monitoring output
gray
6
FI1A
Enable input for channel 1
pink
7
0V
Ground, DC 0 V
blue
8
RST
Reset input
red