System Manual Safety Switch CES-AP-C.2-CH
15
System status table
Operating mode
Actuator/door posi
-
tion
Safety outputs OA and OB
LED indicator
output
State
ST
ATE (gr
een)
DIA (r
ed)
Normal operation
closed
on
Normal operation, door closed
closed
on
flashes
quickly
Hz
Normal operation, door closed, actuator in the boundary area
Re-adjust door
open
off
1 x
Normal operation, door open
Fault display
closed
off
x
Defective actuator (e.g. fault in code or code not readable)
X
off
4 x
Output fault (e.g. short-circuit, loss of switching capability)
X
off
5 x
Internal fault (e.g. component faulty, data fault)
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 seconds at 10 Hz
x
LED flashes three times, and this is then repeated
X
Any state
After the cause has been remedied, faults can generally be reset by opening and
closing the door. If the fault is still displayed afterward, use the reset function or
briefly interrupt the power supply. Please contact the manufacturer if the fault could
not be reset after restarting.
Important!
If you do not find the displayed device state in the System status table, this
indicates an internal device fault. In this case, you should contact the manufac-
turer.