Non-Contact Safety Switch CES-I-AS2A-C04
EN
10. System status table
Operating mode
Actuator/door po
-
sition
CES LED indicator
Output
State
ST
ATE (gr
een)
DIA (r
ed)
Normal operation
closed
Normal operation, door closed
closed
Flash burst
inverse
5 x
Normal operation, door closed, actuator in the limit range
¨
Re-adjust door
open
1 x
Normal operation, door open, no actuator taught
open
2 x
No actuator taught, teach-in operation not completed successfully
Teach-in operation
(only unicode)
open
3 x
- Door open, device is ready for teach-in for another actuator (only short time after power
UP)
- Switches that have not been taught-in remain in teach-in standby until the teach-in opera-
tion starts
closed
1 Hz
Teach-in operation
X
Positive acknowledgment after completion of teach-in operation
Fault display
closed
3 x
Defective actuator (e.g. fault in code or code not readable)
X
Internal fault (e.g. component faulty, data error)
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 seconds at 10 Hz
3 x
LED flashes three times, and this is then repeated
X
Any state
After the cause has been remedied, faults can generally be reset by opening and closing the guard. If the fault is still dis-
played afterward, briefly interrupt the power supply. Contact the manufacturer if the fault could not be reset after restarting.
Important!
If you do not find the displayed device status in the system status table, this indicates an internal device
fault. In this case, you should contact the manufacturer.