Operating Instructions
Non-Contact Safety Switch CES-AR-C.2-…
24
(Translation of the original operating instructions) 2109309-09-03/20
11.1.1. Typical system times
Refer to the technical data for the exact values.
Ready delay
: After switch-on, the device carries out a self-test. The system is ready for operation only after this time.
Turn-on time of safety outputs
: The max. reaction time t
on
is the time from the moment when the actuator is in the actu-
ating range to the moment when the safety outputs switch on.
Simultaneity monitoring of safety inputs IA/IB
: If the safety inputs have different switching states over a certain time,
the safety outputs (OA and OB) will be switched off. The device switches to the fault state.
Risk time according to EN 60947-5-3
: If an actuator moves outside the actuating range, the safety outputs (OA and OB)
are deactivated at the latest after the risk time.
If several devices are operated in a series connection, the risk time of the overall device chain will increase with each device
added. Use the following calculation formula:
t
r
= t
r, e
+ (n x t
l
)
t
r
= Total risk time
t
r, e
= Risk time, single device (see technical data)
t
l
= Risk time delay per device
n = Number of additional devices (total number -1)
Discrepancy time
: The safety outputs (OA and OB) switch with a slight time offset. They have the same signal state no
later than after the discrepancy time.
Test pulses at the safety outputs
: The device generates its own test pulses on the safety outputs (OA and OB). A down-
stream control system must tolerate these test pulses.
This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for
your control system or if shorter test pulses are required, contact our support organization.
The test pulses are also output when the safety outputs are switched off.