NORD
canopy
|
EOZ installation guide
6. Measure and adjust airflow
1. Measure the airflow at the KRI damper installed before the EOZ to find operational airflow of the unit. For
more information refer to
KRI regulating damper installation guide
.
2. Measure the air pressure difference of the EOZ unit from both nozzles as seen in the picture (both
measurements need to be approximately the same).
Confirm that the system airflow and pressures fall within the following specifications:
Model
Operational airflow
(l/s)
1
Pressure difference
(Pa)
2
Pressure drop
(Pa)
EOZ-1
30
-20
35
EOZ-2
50
-25
30
1
2