Please follow below instructions in order to copy parameters;
0-50: First must be set to 1 and press OK, all the parameters inside the driver are transferred to Keypad
0-50: After must be set to 2 and press OK, all the parameters inside Keypad are transferred to the
driver
0-50: if set to 3 and press OK, all the parameters except Motor power inside Keypad are transferred
to the driver
Relay Terminals;
01: COM
02: NO
03: NC
Parameter
No
Parameter Name
Set Value
0-40
[Hand On] Key on LCP
0=OFF
0-41
[Off / Reset] Key on LCP
2= only Reset active
1-00
Configuration Mode
0= Speed Open Loop (Factory Setting
1-01
Motor Control Principle
0= U/F
1-20
Motor Power
Must be set to value on motor label
1-22
Motor Voltage
Must be set to value on motor label
1-23
Motor Frequency
Must be set to value on motor label
1-24
Motor Current
Must be set to value on motor label
1-25
Motor Nominal Speed
Must be set to value on motor label
1-71
Start Delay
1.0 sec
3-15
Reference Resource 1
1= Analog input 53 (Factory setting)
3-41
Ramp 1 Ramp up Time
Must be set according to the product and motor (ie. 3.00 sec)
3-42
Ramp 1 Ramp Down Time
Must be set according to the product and motor (ie. 3.00 sec)
4-12
Motor Speed Low Limit [Hz]
25.00 Hz
4-14
Motor Speed High Limit [Hz]
50.00 Hz
5-10
Terminal 18 Digital Input
8= Forward start (Factory setting)
5-12
Terminal 27 Digital Input
1= Reset (Factory Setting)
5-40
Function Relay
2= Driver Ready
6-10
Terminal 53 Low Voltage
Must be set to 5 .00 V
6-11
Terminal 53 High Voltage
10.00 V (Factory setting)
6-14
Terminal 53 Low Ref./Feedb. Value
25 Hz.
6-15
Terminal 53 High Ref./Feedb. Value
50 Hz.
14-20
Reset Mode
5= Automatically reset 5 times
14-90 [7]
High Current Reset
must be set 4 (automatic reset after 3 minutes)
12
Forw
ar
d S
tart
0-10 V. input
AI1 Com