South Bend, Indiana USA
|
networketi.com
FPT-130 INSTALLATION MANUAL |
PART NO.
25165
REV
F
4
INSTALLATION
The FPT 130 Automatic Heat–Trace Control should be
LQVWDOOHG E\ D TXDOLƓHG OLFHQVHG HOHFWULFLDQ ,QVWDOODWLRQ
must conform to all applicable local and national electrical
codes and laws. The unit’s NEMA 4X IP66 enclosure allows
for indoor or outdoor applications.
The FPT 130 controller has an ambient operating
WHPSHUDWXUHUDQJHRIŧr)WRr)ŧr&WRr&
To avoid potential internal condensation mount the unit
out of direct sunlight.
,QVWDOOWKH)37RQDƓ[HGŴDWYHUWLFDOVXUIDFHXVLQJWKHXQLWōV
PRXQWLQJŴDQJHV7KHPRXQWLQJŴDQJHVDFFRPPRGDWH
1/4” or 6.3 mm fasteners.
The FPT 130’s nonmetallic enclosure has one 1.046”
hole for conduit entry; this can hold both power and
load wiring.
Use only Listed Type 4X IP66 liquid–tight conduit hubs
or cable glands. Connect the hub to the conduit system
before connecting the hub to the enclosure.
The unit comes with two installed liquid–tight cable
JODQGV2QHRIWKHVHƓWWLQJVLVIRUWKHWHPSHUDWXUHVHQVRU
cable, and the other is for the alarm relay cable.
The cable glands can accommodate cable diameters
0.08” to 0.24” (2 mm to 6 mm). The temperature sensor
may be located up to 2,000’ (610m) from the FPT.
There is a removable electrical insulation divider that
must be in place when there is power applied to the unit.
All leads should be terminated; no unsecured leads
should be left inside the wiring compartment.
JP1
JP2
FPT130
Thermistor
Fault
FPT130
Set
Point
GPT
Heat On
Fir
e Pr
ot
Lock
Heat Off
1
0
1
1
0
0
1
0
0
1
50F
45F
30F
38F
TEMPERATURE SENSOR
ALARM RELAY
Figure 1
Thermistor
The FPT 130 wiring layout
INPUT POWER
Line:
Neutral:
Ground:
BLACK / Line 1
WHITE / Line 2
GREEN
HEATER CABLE
Line:
Neutral:
Ground:
BLACK / Line 1
WHITE / Line 2
GREEN
Heat Tracing Sales Mt. Airy, MD (410) 795-2223 www.heattracingsales.com