INSTALLATION
The system installation with the EUR–5A snow and ice
melting control should be performed by a qualified,
licensed electrician. The installation and all electrical
connections should conform to the NEC (ANSI/NFPA
70) in the United States of American, to the Canadian
Electrical Code in Canada, and to all applicable local
electrical codes and laws.
The EUR–5A and ETI sensors are Class 2 devices and
utilize Class 2 wiring. The EUR–5A should be housed in
a protected location that meets local electrical code.
The EUR–5A can be mounted in the same panel as the
heater contactors, as long as no unrelated circuits are
present and the required internal spacings and barriers
are implemented. If the EUR–5A needs to be located in an
area where it might be exposed to environmental hazards
the EUR–5A should be housed in a NEMA enclosure
suited for the local environment.
Make sure that your installation and all electrical connections conform to the NEC (ANSI/NFPA 70) in the
United States of American, to the Canadian Electrical Code in Canada, and to all applicable local electrical
codes and laws. The EUR–5A, RCU–3, and ETI environmental sensor are all rated as NEC Class 2 devices.