Electrical Test Instruments PI-2500 and PI5000
Section IV - Operating Instructions
==============================================================================
==============================================================================
Copyright(C) 1994-2008 Electrical Test Instruments, LLC. All Rights Reserved
Page IV-18
12.
Press RESET button.
13.
Set MAC-20 to N.C. mode. Set MAINTAIN on.
14.
Press and release INITIATE button; OUTPUT ON light should glow, timer
should operate, and current should indicate on display.
15.
When the relay control circuit contacts open, the test set output should
deenergize and the timer should stop.
16.
Read and record the test value of current and the time of the test. Com-
pare the results to the manufacturer's specifications. If possible, adjust the
relay. Usually, if the relay time of operation is incorrect, it is necessary to re-
place the relay heater with one of the recommended sizes for the motor
being protected. If a check test is desired, the relay must be allowed to cool
for a period of time (approximately 15 to 30 minutes).
17.
For a multi-pole relay, repeat the above tests for the other relay poles.
18.
Shut down test set, disconnect breaker, and prepare for subsequent test-
ing or relocation according to steps 18 through 22 in pre-test installation
and setup outlined above.