EX73900 Series Hardened Managed Ethernet Switch

 

EX73900 rev. 3.0 

04/13/2018 

Installation Guide

 

 

  

W70G-EX73900Q3

 

 

Pin 

Description 

Power 1 

+

  12-48VDC 

  Power Ground 

Power 2 

+

  12-48VDC 

  Power Ground 

 

Earth Terminal 

Relay Output Rating 

2A @ 30VDC 

Relay Output Alarm

 

The relay output can be connected to an alarm 

signaling device. Current is 2A at 30VDC. 

 

Power-Up Sequence 

When the switch is powered up: 

 

All 

Link/ACT

 LEDs blink momentarily. 

 

The 

Power 1, 2 

LEDs light up and stay lit.  

 

LEDs for every port connected to a device 

will flash, as the switch conducts a brief 

Power On Self-Test (POST). 

 

Console Configuration 

 

Connect to the switch console by 

connecting the DB9 cable to the console 

port of the switch and to the serial port of 

the computer running a terminal emulation 

application (such as HyperTerminal or 

Putty).  

 

Configuration settings of the terminal-

emulation program: Baud rate: 115,200bps, 

Data bits: 8, Parity: none, Stop bit: 1, Flow 

control: none. 

 

The default login name is “root,” no 

password. 

Web Configuration 

 

Log in to the switch by launching a web 

browser and entering 192.168.1.10 in the 

address bar. 

 

Enter the default login ID: root (no 

password) and click “Login.” The system 

information screen will display. 

Other information 

DIN-Rail Assembly Startup, and Dismantling 

 

Assembly: Place the Switch on the DIN rail 

from above using the slot. Push the front of 

the Switch toward the mounting surface 

until it audibly snaps into place. 

 

Startup: Connect the supply voltage to 

start up the Switch via the terminal block. 

 

Dismantling: Pull out the lower edge and 

then remove the Switch from the DIN rail. 

 

 

 
 

Power wiring information: 
Use cable type - AWG (American Wire Gauge) 18-

24 and corresponding pin type cable terminals. 

 

Using torque value 1.7 lb-in, do not use excessive 

force when fixing wiring. 

 

 The rating of the power wire used must be 

at least 105°C. 

 

 

Label clean up: 

Indoor use and pollution degree II, it must 

be wiped with a dry cloth for clean up the 

labelling. 

 

If the equipment is used in a manner not 

specified by the manufacturer, the 

protection provided by the equipment may 

be impaired. 

 

The Ethernet switch shall be mounted in the 

Industrial Control Panel and ambient 

temperature should not exceed 75 °C.

 

Manufacturer information: 
ETHERWAN SYSTEMS, INC. 
4F-7, No. 79, Sec. 1, Xintai 5th Road, Xizhi 

District, New Taipei City 221, Taiwan 

 

 

Altitude up to 2000 m 

 

Indoor use only 

 

Humidity range (Operational): 5% to 95%, 

non-condensation 