background image

5

Installation and Maintenance

Apply to flue gas condensing water heater and breeching condensate drains only.

DO NOT

 exhaust flue gases through the Neutralizer Kit. It is not rated for water heater flue gases. 

Operating the Neutralizer Kit as an exhaust vent can cause injury or death from carbon monoxide. 

DO NOT

 combine vent condensate drain lines and water heater condensate lines. Use a separate Neutralizer 

Kit for each application.

Neutralizer Kit must be installed below system P-traps, water heater and breeching condensate drains.

Gas traps must be installed between the water heater, vent drains, and water condensate outlet and the inlet of 

Neutralizer Kit.

Before operating the water heater, fill the Neutralizer Kit and traps with tap water.

NEVER

 operate with Kit or P-Traps dry.

Kit should be recharged yearly (every 2,000 operating hours) or when pH level moves below 6.

Failure to comply with these guidelines could result in severe personal injury, death, or property damage.

WARNING

!

!

Maintenance Instructions:
Installer:

 Instruct the building owner to frequently inspect the Neutralizer Kit and all condensate connections. The 

owner must notify a qualified technician if any problems are noticed.
Instruct the building owner to schedule an annual (or every 2,000 operating hours) recharge of the Neutralizer Kit. 

Contact Grand Hall for replacement parts.

Reviews: