Eterna TLS68EX Installation Instructions Download Page 2

READ THIS FIRST:

Check the pack and make sure you have all of the 

parts listed on the front of this booklet. If not, 

contact the outlet where you bought this product.

This time delay switch must be installed by a 

competent person in accordance with the Building 

Regulations making reference to the current edition 

of the IEE Wiring Regulations (BS7671).

As the buyer, installer and/or user of this product it 

is your own responsibility to ensure that it is fit for 

the purpose for which you have intended it. Eterna 

Lighting cannot accept any liability for loss, damage 

or premature failure resulting from inappropriate 

use.

This product is designed and constructed according 

to the principles of the appropriate British Standards 

and is intended for normal service. 

Switch off the mains before commencing installation 

and remove the appropriate circuit fuse.

Do not overload the switch; check that the total 

wattage and start up surge current (if any) of the 

connect load does not exceed the maximum 

specified.

Disconnect the switch from the electrical supply 

before flash or high voltage testing.

Suitable for indoor and outdoor use.

Before making fixing hole(s), check that there are no 

obstructions hidden beneath the mounting surface 

such as pipes or cables. If your switch is part of the 

provision of a new electrical supply, the supply 

must conform with the requirements of the Building 

Regulations making reference to the current edition 

of the IEE Wiring Regulations (BS7671).

Make connections to the electrical supply in 

accordance with the following code:

Live - Brown or Red 

Neutral - Blue or Black

NOTE:

 This is not a two-wire system and requires 

neutral connection.

When making connections, ensure that the terminals 

are tightened securely and that no strands of wire 

protrude. Check that the terminals are tightened 

onto the bared conductors and not onto any 

insulation.

This switch is double insulated; do not connect any 

part to earth.

You are advised at every stage of your installation to 

double-check any electrical connections you have 

made. After you have completed your installation 

there are electrical tests that should be carried out: 

these tests are specified in the Wiring Regulations 

(BS7671) referred to in the Building Regulations

LOAD SPECIFICATION:

Incandescent lighting loads - 16A maximum.

Fluorescent lighting loads - 6A maximum.

Compact fluorescent/low energy lighting loads - 3A 

maximum.

Low voltage lighting loads - 3A maximum.

LED load 300W.

NOTE:

 a maximum of 6 fluorescent light fittings is 

recommended with total power factor correction 

capacitance not exceeding 40μf.

Fans and ventilation equipment – 3A maximum.

SON light fittings must be switched via a contactor 

or other external relay. If you are using this switch to 

control magnetic switch start fluorescent fittings and 

your light fittings strike inconsistently, a power factor 

correction capacitor may be required. If your light 

fitting flickers or fails to turn off correctly, this is most 

likely to be due to incorrect or missing power factor 

correction. 

Check with the manufacturer of the light fitting and/

or supplier of power factor correction capacitors for 

the exact specification required for your installation. 

A minimum of 1μF for each fitting may be connected.

INSTALLATION:

01.   Choose the location for your new switch 

according to the conditions above.

02.  Undo the large screws in each corner of the front 

of the switch and lift off the lid.

03.   Mark the positions of the fixing holes at the 

corners of a rectangle 62mm wide x 92mm high.

04.  Prepare the fixing holes and insert wall plugs if 

necessary.

05.  Whether you are intending to use cable glands 

or conduit to make your cable entry, you will 

need to make hole(s) in the rear half of the case to 

accept your chosen fitting.

06.  Secure the rear half of the case to the wall using 

suitable fixings.

07.  Make the electrical connections according to the 

colour code on previous page.

08.  Set the desired “on” time by combination of dip 

switches and the rotary control, see Fig 1. and 

table below.

09.  Close the switch case and tighten the screws. 

Take care not to over-tighten.

10.  Restore the mains power and wait 20 seconds for 

the switch to stabilise.

11. Activate the switch and check the “on” time.

12.  If the time “on” requires further adjustment, turn 

of the power at the mains before opening the 

switch case. Remember to wait 20s after restoring 

the power before activating the switch again.

 

TRIGGER FUNCTION:

The timer can be triggered by applying a live 

connection to the “trigger” terminal. This can be 

done using a momentary switch for example, in 

lighting applications; or an unswitched link for 

applications such as extractor fan over-run.

 

MULTI-POINT SWITCHING:

For switching the load from multiple locations simply 

connect two or more units in parallel. 

NOTE: 

All switches must share the same power 

supply.

SWITCH SETTING

TIMER FUNCTION

1

2

3

4

0

0

1

0

2 seconds to 50 seconds

1

0

1

0

50 seconds to 20 minutes

1

1

1

0

20 minutes to 70 minutes

1

1

0

0

70 minutes to 2 hours

0

0

0

1

Timer function disabled

On

0

Reviews: