Eterna SDION Installation Instructions Download Page 2

READ THIS FIRST:

Check the pack and make sure you have all of the parts 

listed on the front of this booklet. If not, contact the 

outlet where you bought this product.

This fitting must be installed in accordance with the 

Building Regulations. These may be obtained from 

HMSO or viewed and downloaded from www.odpm.gov.

uk following the link for Building Regulations.

Switch off the mains before commencing installation 

and remove the appropriate circuit fuse.

Suitable for indoor use only.

This product is only suitable for use in living areas (not 

for areas constantly subject to moisture).

The smoke alarm must not be exposed to dripping or 

splashing.

Before making fixing hole(s), check that there are no 

obstructions hidden beneath the mounting surface such 

as pipes or cables.

The chosen location of your new alarm should allow 

for it to be securely mounted (e.g. to a ceiling joist) and 

safely connected to a mains supply.

Do not attach to surfaces which are damp, freshly 

painted or otherwise electrically conductive  

(e.g. metallic surfaces).

If the location of your new alarm requires the provision 

of a new electrical supply, the supply must conform to 

the requirements of the Building Regulations.

This product is designed for permanent connection 

to fixed wiring: this should be either a suitable circuit 

(protected with a 5 or 6 Amp MCB or fuse) or a fused spur 

(with a 3 Amp fuse) via a fused connection unit.

Make connections to the electrical supply in accordance 

with the following code:

Live 

  Brown or Red 

Neutral    Blue or Black 

Yellow  

  Connect between multiple alarms

This fitting is double insulated, DO NOT CONNECT ANY 

PART TO EARTH.

Cable of at least 0.75mm

2

 cross-sectional area must be 

used to connect to the supply and between alarms.

You are advised at every stage of your installation to 

double-check any electrical connections you have made. 

After you have completed your installation there are 

electrical tests that should be carried out: these tests are 

specified in the Wiring Regulations (BS7671) referred to 

in the Building Regulations.

 

LOCATINg THE SmOkE ALARm:

This smoke alarm is a multi station ionisation alarm and 

can be connected to other smoke alarms of the same 

make and type. This interconnect feature allows up 

to 40 smoke detectors to be connected together over 

a distance of 150 metres maximum, using the single 

yellow wire thus allowing all smoke detectors to sound 

when one is activated. This smoke detector cannot be 

connected to any other device such as a fire alarm panel.

If your dwelling is on a single storey, for minimum 

protection you should fit an alarm in the hallway 

between the living areas (including kitchens) and the 

sleeping areas. Place it as near to the living areas as 

possible and ensure that alarm is audible when the 

bedrooms are occupied. See Fig.1 below.

If your dwelling is multi-storey, for minimum protection, 

one alarm should be fitted at the bottom of the staircase 

with further alarms fitted on each upstairs landing. 

This includes basements but excludes crawl spaces and 

unfinished attics. See Fig. 2 below.

NOTE: 

For maximum protection, an alarm should be 

fitted in every room (except kitchen, bathroom and 

garage).

DO NOT FIT A SmOkE ALARm IN THE kITCHEN OR 

BATHROOm,

 as cooking fumes and steam may trigger 

the alarm.

DO NOT FIT A SmOkE ALARm IN A gARAgE

 as exhaust 

fumes could trigger the alarm.

The smoke alarm should be located at least 300mm 

away from a light fitting. See Fig. 3 below.

POSITIONINg THE SmOkE ALARm:

As smoke rises, it is advisable to mount the alarm on a 

ceiling in a central position. Avoid areas where there is 

no air circulation e.g. corners of rooms and keep away 

from anything that might obstruct the free flow of air. 

If wall mounting, do not mount tight into corners. On 

sloping ceilings, mount 900mm from the apex measured 

horizontally. See Fig. 4 below.

Areas to be avoided include the following:

•  Locations where the ambient temperature may fall 

below 4°C or rise above 40°C.

•  Humid areas such as bathrooms, kitchens, or shower 

rooms where the relative humidity may exceed 90%.

•  Fume filled environments such as garages. Exhaust 

gases may cause false alarms.

•  Adjacent to or directly above hot objects such as 

radiators or wall vents that can affect the direction of 

air currents.

•  In very dusty or dirty environments such as workshops.

 INSTALLATION:

 

 

01. Remove the base plate from the alarm.

02.   Using the mounting plate as a template mark the 

position of the fixing holes.

03.  Place base plate over fixing holes and secure using 

the wall plugs and screw supplied, (if wall plugs and 

screws supplied are not suitable for your application 

use suitable alternatives).

04.  Connect the power connector to the incoming mains 

supply observing the wiring colour code opposite. If 

multiple smoke alarms are not to be interconnected, 

isolate the yellow wire in a separate terminal block 

and wrap well with insulation tape.

05.  When smoke alarms are to be interconnected, 

connect all of the yellow wires together.

06.  If the smoke alarms are to be locked into position, 

remove the two tamper-proof tabs from the 

mounting plate and retain for use later.

07.  Insert the 9V battery into the smoke alarm noting 

the polarity of the connections. Ensure the metal tab 

is fully depressed when the battery has been fitted. 

Note: For safety of the end user the smoke alarm 

cannot be fitted without its battery.

08.  Before assembly to the base plate test the correct 

operation of the smoke detector (operating from the 

battery only) by pressing the test button on the front 

of the detector. The unit should emit a loud pulsing 

alarm.

09.  Connect the power connector into the socket on the 

rear of the smoke detector. Note: This is a polarized 

connector and can only be plugged in one way.

10.  Assemble the detector onto the base plate by 

aligning the two projections on the base plate with 

the two keyhole slots in the detector. Lock in position 

by turning clockwise.

11.  Insert the two tamper-proof tabs in the slots 

provided in the side of the unit. Once fitted the 

detector can only be removed from the base plate 

by first removing these tabs,  gently prising them out 

with a screw driver.

12. Replace the circuit fuse and restore the power.

13.  Test the correct operation of the smoke detector by 

pressing the test button on the front of the detector, 

the alarm should emit a loud pulsating alarm.

Fig 2

Fig 4

Fig 5

Fig 1

Bedroom 

Bedroom 

Hall 

Bedroom 

Bedroom 

Living Room 

Kitchen 

KEY:            Maximum Protection

Bathroom 

Bedroom 

Kitchen 

Basement 

Landing  Bathroom 

Living 

Room 

Hall 

Fig 3

Ceiling

1 metre

Best in 

centre 

of 

room

Dead air space 

- do not mount 

in this area

15

cm

 m

im

30

cm m

ax

900mm

Live (Brown)

Interconnect (Yellow)

Neutral (Blue)

Live (Brown)

Interconnect (Yellow)

Neutral (Blue)

Pg 2

Pg 3

Reviews: