ETCR 3000 Manual Download Page 14

 

-11- 

There  are  3  types  of  display  modes  for  earth  ground  resistance 

measurement:   

P

---- Average Value Display 

H

---- Maximum Display 

L

---- Minimum Display 

The default display on booting is average value, and press 

MODE

 button 

to switch display mode. 

Precision  measurement  earth  ground  resistance  adopts  three-wire 

connection.  After  connection  of  auxiliary  earthing  rod  and  testing  wires,  set 

FUNCITON

  rotary  switch  to  "2000

Ω

",  press  "START"  button  to  start 

measuring.    During  measurement,  LED  indicator  flashes,  LCD  count  down 
displays,  and  after  measurement,  LCD  displays  measured  values.  If  the 
display values are too small, set it to "200

Ω

", "20

Ω

" in turn, that is to choose 

the most appropriate gear position for measurement. The value displayed on 
the most appropriate position is the measured earth ground resistance value.   

After  measurement,  press 

MODE

  button  to  check  for  the  maximum, 

minimum and average value in this measurement.   

After measurement, it may  delete  current measured values by  pressing 

CLR

 button.   

 

7

Simple Measurement 

 

When  select  commercial  use  power  supply  system  earth  as  auxiliary 
earth electrode, it must use detector to confirm that is it the earth ground 
electrode for commercial use power supply system. 

 

 

It is forbidden to use this Tester to confirm earth electrode of commercial 
use power supply system 

 

This  method  is  a  simple  method  for  measurement  that  does  not  use 

auxiliary  earthing  rod,  taking  the  earth  electrode  with  the  minimal  existing 
earth ground resistance value as auxiliary earth electrode, and connecting by 
two simple testing wires (in which C, P interfaces are in short circuit). It can 
make  use  of  metal  pipes,  fire  hydrants  and  other  metal  buried  objects, 
common earthing of commercial electric power system or lightning protection 
earth ground electrode and others to replace auxiliary earthing rods C, P, and 
pay  attention  to  remove  oxide  layer  on the  connection  point  of the  selected 
metal auxiliary earthing object when making measurement.   

Earth  ground  resistance  simple  testing  wire  connection  is  as  following 

figure, and refer to precision measurement for other operations.   

                                                                               

 

                                       

 

 

       

Summary of Contents for 3000

Page 1: ......

Page 2: ......

Page 3: ...I Operation Methods 8 1 Switch On Off 8 2 Battery Voltage Check 8 3 Insert and Connection of Rods 8 4 Earthing Voltage Measurement 9 5 Wire Resistance Verification 10 6 Precision Measurement 10 7 Simple Measurement 11 8 Backlight Control 13 9 Alarm Settings 13 10 Data Lock Storage 13 11 Data Reading Deletion 13 12 Data Upload 14 VIII Battery Replacement 14 IX Accessories 15 ...

Page 4: ...uring measuring u Pay attention to words and symbols stick on the Tester u It shall make sure that tester and accessories are in good condition before use it can be used only when there is no damaged naked or broken part in testing wires or insulation layer u During measurement it is forbidden to touch bare conductors and circuit under measurement u Before measurement please confirm whether FUNCTI...

Page 5: ... no auto shut off function Please set FUNCTION rotary switch to OFF after usage u When the meter displays battery low voltage symbol and you need to replace the battery in time u If the Tester is not going to be used for a long period remove the battery u Pay attention to measuring range and usage environment stipulated for the Tester u This measuring device is only to be used disassembled adjuste...

Page 6: ...ion more accurate on measuring on site low value earth ground resistance which can avoid error caused by resistance change due to prolonged usage of testing wire avoid error caused by testing wire that is failed to be fully inserted into tester interface or by poor contact avoid error caused by users replacing or lengthening testing wires ETCR3000 Digital Earth Resistance Tester is composed of hos...

Page 7: ...de Precise 3 pole measurement simple 2 pole measurement Measuring Method Earth ground resistance rated current change pole method measurement current 3mA Max 820Hz Voltage to ground average value rectification Data Mode Average value maximum minimum Wire Resistance Verification Avoid error caused by testing wire that is failed to be fully inserted into tester interface or by poor contact or by use...

Page 8: ...h display FULL icon to indicate storage is full Data Hold Data hold function HOLD icon display Data Read Data read function READ icon display Overflow Display Exceeding measuring range overflow function OL icon display Alarm Function When measuring value exceeds alarm setting value there is Toot toot toot alarm hint Battery Voltage When battery voltage decreases to about 7 8V battery voltage low i...

Page 9: ...sulation Resistance Over 10MΩ between circuit and enclosure it is 500V Withstanding Voltage AC 3700V rms Between circuit and enclosure Electromagnetic Features Wireless frequency electromagnetic field Protection Type IEC61010 1 IEC1010 2 31 IEC61557 1 5 IEC60529 IP54 Pollution etc 2 CAT Ⅲ 300V IV Tester Structure ...

Page 10: ...ent with fall of potential method AC constant current I 3mA Max 820Hz is applied between the measurement object E earth electrode and C current electrode and finding out the potential difference V between E and P potential electrode Rx V I 3 Maximum Operating Error Operating error B is an error obtained within the rated operating conditions and calculated with the intrinsic error A which is an err...

Page 11: ...itch on and off When rotary switch button displays OFF for shut off The Tester has no auto shut off function so please shut it off after usage in case of battery consumption saving 2 Battery Voltage Check After switch on if LCD displays low battery voltage icon which indicates that battery voltage is low and please replace the battery in compliance with instructions Adequate battery power can ensu...

Page 12: ...in the case of short circuit of P C interface Otherwise measuring voltage in the earthing circuit of cutout switch may cause cutout switch start On measuring earthing voltage please do not impose over 600V voltage on measurement connectors On measuring earthing voltage please do not touch measured bare conductors in case of electric shock After connecting of auxiliary earthing rod and testing wire...

Page 13: ...ce value and stores it For this time switch on it will automatically deduct the verified wire resistance value from earth ground resistance measurement It will not preserve the verified wire resistance value on switching off It needs re verification for next time switching on 6 Precision Measurement Please make sure testing wire plug has been totally inserted into testers corresponding interface a...

Page 14: ...t measured values by pressing CLR button 7 Simple Measurement When select commercial use power supply system earth as auxiliary earth electrode it must use detector to confirm that is it the earth ground electrode for commercial use power supply system It is forbidden to use this Tester to confirm earth electrode of commercial use power supply system This method is a simple method for measurement ...

Page 15: ... resistance value of common earthing object like commercial use power system Then the earth ground resistance value of measured earthing object is RX RE re Adopting simple method for measurement of earth ground resistance shall try to select the earthing object with low value as the auxiliary earth ground electrode and thus the tester reading value can be more approaching to true value Please take...

Page 16: ...ess button for a long time about 3 seconds to enter alarm critical value settings press or to change current digital press button to move cursor and then press button to store and exit When measurement value is larger than alarm critical settings value and it has opened alarm function the Tester will flash and display icon and give out toot toot toot alarming sound 10 Data Lock Storage Startup or ...

Page 17: ...nd the connection is successful then it can read the stored historical data upload to company and preserve Monitoring software has the function of online real time monitoring and historical inquiry dynamic display with the maximum minimum and average value indication with alarm value settings and alarm indicator and the function of historical data access reading preserve print and other functions ...

Page 18: ...ag 1 PC Auxiliary Earthing Rod 2 PCS Monitoring Software Disk 1 Copy RS232 Communication Cable 1 PC Testing Wire 3 PCS Simple testing wire 2 PCS Zinc manganese dry battery 6 PCS R14S 1 5V Manual Warranty card Qualification Certificate 1 Copy ...

Page 19: ......

Page 20: ... Electronic Technology Company Address F 3F No 4 Pengshang Zhifu Road Jiahe Baiyun District Guangzhou Guangdong China Post Code 510440 Tel 86 20 62199556 62199553 Fax 86 20 62199550 E mail info etcr cc Website www etcr cc ...

Reviews: