E T C   I n s t a l l a t i o n   G u i d e

Wall Mount Station Power Supply

Wall  Mount  Station  Power  Supply

Page 2 of 3

Electronic Theatre Controls, Inc.

Rough-In Conduit and Wiring

Knockouts are provided on top and bottom for conduit access into the unit. All wiring terminations are 
accessible from the front of the unit with the cover removed.

Required terminations include -

• A single phase 115 VAC, 230 VAC, or 240 VAC power input (two wire) which terminates to the 

power input terminal block, plus a ground wire which terminates to the ground bar screw terminal.

• A single run of Belden 8471 plus one 14 AWG (1.6mm) Echo station ESD ground wire.

Terminate Wiring

Connect Power

Supply a single phase of 115 VAC or 230/240 VAC (2 wire plus ground) to the AC input terminals.

Step 1:

Connect the Line (Hot) wire to the terminal labeled “L”.

Step 2:

Connect the Neutral wire to the terminal labeled “N”.

Step 3:

Connect the Protective Earth (ground) wire to the ground terminal.

N o t e :

All low voltage control cables must run in separate conduit from power wires.

AC Input - 2 wire plus 

Protective Earth (ground)

ESD Ground terminals - Echo station 

ESD ground wires terminate here

Control wiring - Belden 8471

voltage barrier