ETC Installation Guide

P-NSPS-D

LED Status Indicators

Power - indicates blue when LinkConnect bus power is present

Bus Fault - indicates red when there is a LinkConnect bus fault, meaning
Net A and Net B are shorted to Ground (Earth).

Note:

If the Network Station Power Supply is powered on with the

LinkConnect bus wires (Net+ and Net-) shorted, the Power indicator
will remain dark.

Error - indicates red when local or system errors are present

Error Messages

Errors that are present in the system will display on the Status screen and will
automatically clear themselves if the condition is resolved.

Error

Description

Resolution

<name> Lost

This P-NSPS-D has

lost communication

with the <P-ACP>

<name>

Unconnected

This P-NSPS-D has

booted without

communication

from a <P-ACP>

P-ACP

Unconnected

This P-NSPS-D has

not received

incoming P-ACP

communications.

This message is shown either at initial

installation and power up or when the

Network Station Power Supply has never

received P-ACP communications.

Ethernet

Connection

Lost

This P-NSPS-D does

not have an Ethernet

connection.

This error will suppress all other messages.

P-NSPS-D

Page 6 of 8

ETC

Summary of Contents for P-NSPS-D

Page 1: ...e LinkConnect station communication bus The Network Station Power Supply consists of two components that must be used together the DIN rail Network Station Power Supply that powers the station communi...

Page 2: ...r Supply voltage output terminals and the P NSPS D No other connections are supported Network Station Power Supply Input Use the ETC supplied 48 VDC power pigtail blue and black wire pair with the thr...

Page 3: ...comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is o...

Page 4: ...D a Run up to four LinkConnect data runs Belden 8471 or equivalent to the P NSPS D Strip 7 mm 1 4 in from the ends of each b Terminate the data wire typically white from one wire pair to terminal A a...

Page 5: ...ire into the L terminal and the neutral wire to the N terminal Secure each wire in place using a 3 mm slotted screwdriver Torque to 5 kgf cm 4 4 Lb in 7 Connect to the Paradigm control network by conn...

Page 6: ...resent in the system will display on the Status screen and will automatically clear themselves if the condition is resolved Error Description Resolution name Lost This P NSPS D has lost communication...

Page 7: ...ware Reference the Paradigm LightDesigner online help system for details Preferences Preferences for the Network Station Power Supply such as inactivity time are set in the LightDesigner configuration...

Page 8: ...ng Connected green Connected with Errors red a partial connection with bad comms Lost red comms activity is no longer present Unconnected red no comms present Main Menu About Setup File Operations Set...