System Installation
8
System Installation
This chapter details the installation and wire termination for each BluesSystem product.
Fixture Installation
BlueBeam and BlueDome LED lighting fixtures mount directly to a standard metal or plastic
conduit junction box (either flush mounted or surface mount is acceptable). They must be
powered by a low-voltage power supply, such as a BluesSystem One-Zone or Six-Zone Power
Supply. For more information about power supplies, reference
.
ETC recommends that you install all wiring in grounded metal conduit. When calculating
cable sizes, each fixture consumes 0.13A at 24 VDC or 0.8A at 36V.
Note:
Read this chapter in full before beginning your system installation.
WARNING:
A system without an accessible power disconnect device cannot be
serviced or operated safely. Follow all local codes and restrictions.
WARNING:
The BlueBeam and BlueDome LED lighting fixtures cannot be installed
in the storage area of a clothes closet.
WARNING:
• Do not connect to a mains supply. The fixture requires 11-36 VDC only.
• Do not overtighten mounting screws.
• Always use the supplied gasket.
• Do not allow moisture into rear terminal area.
Note:
All low voltage cables must run in separate conduit from higher voltage (power)
wires. Follow all local codes and restrictions.
BlueBeam Fixture
with Octagonal
Mounting Bracket
BlueDome Fixture
with Round
Mounting Bracket