24
DataTrack System Planning and Installation Manual
Wiring In-line Feeds
1:
Strip ground wire and connect to a 0.25 in (6.35 mm) female quick disconnect terminal (not
supplied). Push terminal onto tap clamp at ground plate. Use provided green wire for connecting
between tap clamp and feed connector terminal.
2:
Strip white Neutral wire and connect to Neutral 1 terminal (N1) of feed connector. Clamp wire
using screw. See
Figure 19
.
:
Figure 19: In-line feed wiring
3:
Measure and strip a new wire (not provided) and connect N1 terminal (Feed Connector 1) to
N1 terminal (Feed Connector 2).
4:
Strip Hot 1 supply wire and connect to a 0.25 in (6.35 mm) female quick disconnect (not
supplied). Push onto the Line tap clamp on the current limiting circuit breaker.
5:
Connect load from current limiting circuit breaker to feed connector terminal L1 using provided
wire.
6:
Measure and strip a new wire (not provided) and connect L1 terminal (Feed Connector 1) to
L1 terminal (Feed Connector 2).
7:
Follow the same instructions for Neutral 2 and Hot 2.
Powering On DataTrack
1:
Place luminaires on track.
2:
Switch current limiting circuit breakers to ON position.
3:
Turn main power supply connector to the ON position.
• The current limiting circuit breakers will automatically switch to OFF if current ratings are
exceeded.
• If current limiting circuit breakers will not remain on: Reduce the wattage on the track so the
total wattage is less than the wattage specified on the current limiting circuit breakers. Turn
the current limiting circuit breakers to ON.