Wireless TimeClock Configuration Guide
18
For the Sweep Interval to be in effect, the scheduled Event must have Sweep
enabled with a set duration. The Sweep feature is available for Action types
Scene
,
ON to Level
, and
OFF
. See
Define Settings for ON to Level
for an example.
1. Select
Sweep Interval
from the TimeClock Settings menu, and press
[Enter] to modify.
2. Press [Up] or [Down] to scroll to the target
Sweep Interval
frequency,
and press [Enter] to select.
Set Timed Hold
The Timed Hold feature sets the duration of the Hold that suspends all
scheduled Events. Timed Hold is set to 120 minutes by factory default to
comply with energy conservation standards. The duration can be set to any
value from 10 to 360 minutes, in 10-minute increments.
1. Select
Timed Hold
from the TimeClock Settings menu, and press [Enter]
to modify.
2. Press [Up] or [Down] to scroll to the target
Timed Hold
duration, and
press [Enter] to select.
Set Flick Warn
Flick Warn is a feature that provides visual warning to occupants in a space
when the next scheduled Event is set to turn the lights OFF. See
. When enabled, the lights flick OFF and ON
once when the OFF action is pending, and stay ON for the duration of the
controller’s configured Flick Warn timer (default 60 seconds). Flick Warn allows
an occupant sufficient time to use a manual lighting control to turn the lights
ON and override a pending OFF action.
1. Select
Flick Warn
from the TimeClock Settings menu, and press [Enter]
to modify.
2. Press [Up] or [Down] to scroll
Yes
or
No
, and press [Enter] to select.
Show Seconds
Set the time display to include seconds.
1. Select
Show Seconds
from the TimeClock Settings menu, and press
[Enter] to modify.
2. Press [Up] or [Down] to scroll
Yes
or
No
, and press [Enter] to select.