background image

3

i

Note:

When a button is pressed and a single Red LED blinks, it is 

an indication that the RPS telegram was transmitted but the 

battery voltage is low (less than 2.2V). 
When the Red LED blinks 3 times on a button press the RPS 

telegram was not transmitted and the battery is critically low 

(less than 2.0 V)

A stuck button will cause a repeating red blink roughly every 5 

seconds

Test Modes

1. To access tests, remove the faceplate and  press the button on the side of the 

unit using a fingernail, pen or small tool. 

2. Press and hold the side button until all LEDs blink (about 5 seconds)
3. Tap the button to scroll through the selections. (see table below) 
4. To select an item, press and hold the button until all the LEDs blink (about 5 

seconds)

Test mode times out after 180 seconds.

Test Menu

Single red blink

REBOOT device

Single yellow blink

Range Confirmation

Single green blink

Reserved for future use

Single green + red blink

DEBUG: Test button pad

Single green + yellow blink

DEBUG: Transmit CM APP Version

Reboot

When  rebooted,    a  successful  switch  start  up  is  indicated  by  a  light  chase  sequence: 

 

green -> yellow -> red repeated three times.

A  weak  battery  will  cause  a  repeating  red  blink  roughly  every  half  second.

 

A stuck button will cause a repeating red blink roughly every 5 seconds

Range Confirmation

Provides visual feedback of the MBI’s signal strength received by a linked Echoflex 

controller.

i

Note:

• 

Disable all repeaters in range

• 

The station should only be linked to one controller 

when running the test

1. To enter Range Confirmation Test  press and hold the side button until all LEDs 

blink (about 5 seconds)

2. Tap the button to scroll through the selections. When the yellow LED is 

blinking, press and hold the side button until all the LEDs blink (about 5 

seconds)

All three LED’s will blink on and off quickly for a second followed by a pause, then 

repeats. When the sensor receives a range confirmation telegram from the linked 

controller,  the  sensor  displays  the  signal  strength  status  for  2  seconds,  see  table 

below.

LED - blinking Signal Strength

Status

Green 

-41 to -70 dBm

Best

Yellow 

-70 to -80 dBm

Good

Red  

-80 to -95 dBm

Not ideal, try moving sensor closer 

None

No linked controllers detected. Move sensor closer or add telegram repeating

The test will repeat every 10 seconds and run for a duration of 180 seconds. 

Summary of Contents for Echoflex MBI-2 Series

Page 1: ...e MBI uses 2 buttons for On OFF operation The ON button has a light bulb icon with light rays to indicate ON The OFF button has a light bulb icon without rays indicating OFF The buttons provide both switching and dimming functionality A quick press of the button provides switching a press and hold will dim lights up ON button and down OFF button when linked to an Echoflex dimming controller A doub...

Page 2: ... to an Echoflex Controller The linking process requires the controller or receiver to be mounted powered and within range of the station to be linked Each receiver can support up to 20 30 switch stations depending on receiver model 1 Activate LEARN or LINK mode at the receiver if necessary refer to the manufacturers documentation 2 For each pair of ON OFF buttons press the ON button three times in...

Page 3: ...indicated by a light chase sequence green yellow red repeated three times A weak battery will cause a repeating red blink roughly every half second A stuck button will cause a repeating red blink roughly every 5 seconds Range Confirmation Provides visual feedback of the MBI s signal strength received by a linked Echoflex controller i Note Disable all repeaters in range The station should only be l...

Page 4: ...s than 2 0V A stuck button will cause the red LED to blink every 5 seconds Equipment Profiles EEP F6 02 02 Light Control ON OFF Dimming Accessories PTM365BP1 Single gang barrier plate for switches PTM365BP2 Dual gang barrier plate for switches Available in White or Gray FCC Part 15 231 Remote Control Transmitters Devices equipped with 902 MHz radio Contains FCC ID SZV TCM515U Contains IC 5713A TCM...

Reviews: