background image

2

Installation

1. The  screw-less  face  plate  has  a  snap  on  design. 

Remove  the  face  plate  by  pressing  down  with 
thumbs on a corner of the  raised area and fingers 
on the back center of the unit. The KSS-UW can 
be  mounted  with  wall  anchors  and  #6  screws 
(not  supplied).  Determine  where  the  station  is 
to be located then hold the switch station to the 
surface  of  the  drywall,  (make  sure  no  studs  are 
behind and ensure the station is level and plumb). 
Mark the locations for the wall anchors using the 
screw  holes  as  a  template,  then  install  the  wall 
anchors.    Screw  the  KSS  to  the  wall  anchors.

 

Alternate mounting: The KSS can be mounted to a mud ring or with a separate 
order item (Barrier kit), it can also be installed on wall outlets. (See Accessories 
section  or  data  sheet  for  ordering  information).    Follow  the  Barrier  kit 
(8188K100X-5) installation instructions. 

2. Snap on both the top and bottom snaps of the faceplate (position the slot on the 

cover plate on the bottom of the switch station).  

3. Test the operation of the station. A slight audible click is expected, and the green 

LED will blink on each card insertion to indicate the message was transmitted 
and the last measured battery voltage is good. The LED blink is visible through 
the keycard plastic 

(ambient light may need to be dimmed to view)

.

i

Note:

When a card is inserted and a single Red LED blinks, it is 

an indication that the message was transmitted but the 

battery voltage is low (less than 2.2V). 
When the Red LED blinks 3 times on a card insertion the 

message was not transmitted and the battery is critically 

low (less than 2.0 V) Replace the batteries immediately.

Lin

king a Station to an Echoflex Controller

The linking process requires the controller or receiver to be mounted, powered and 
within range of the station to be linked. Each receiver can support up to 20-30 switch 
stations and/or sensors, depending on receiver model.

1. Activate the LEARN  button on the controller
2. Insert and extract a card three times in quick succession. 
3. Deactivate LEARN mode at the receiver (LEARN mode will time out after 30 s). 

4. 

Test operation of the station by inserting and extracting the card several times. 
There is an egress timer on the card extraction, wait 40 seconds before re-

inserting the card.

Replacing the Battery

The keycard station must be removed from the wall to access the battery.  The battery cover 

3.28”

[83 mm]

LEDs  

visible 

through 

key card 

plastic

Green

Red

Yellow

Do NOT remove this key card 

plastic from the back assembly.

Summary of Contents for Echoflex Keycard Switch Station

Page 1: ...n LED blink visible through the keycard plastic and a card inserted transmission to linked receivers The KSS is powered by a replaceable CR2032 coin cell battery and has an expected lifetime of 100 000 actuations over 10 years The station will indicate a low battery condition by blinking a red LED once upon any card insertion The keycard station is activated with an 85 60 x 53 98 mm 3 37 x 2 125 c...

Page 2: ...ed and the last measured battery voltage is good The LED blink is visible through the keycard plastic ambient light may need to be dimmed to view i Note When a card is inserted and a single Red LED blinks it is an indication that the message was transmitted but the battery voltage is low less than 2 2V When the Red LED blinks 3 times on a card insertion the message was not transmitted and the batt...

Page 3: ...conds The LED blink is visible through the keycard plastic ambient light may need to be dimmed to view the LED blinks Test mode times out after 180 seconds Test Menu Single red blink Reset Single yellow blink Range Confirmation Single green blink Reserved for future use Single green red blink Factory use only Single green yellow blink Factory use only Reset When reset a successful switch start up ...

Page 4: ...ple red blink indicates the battery voltage is critically low less than 2 0V and should be replaced immediately A stuck button will cause the red LED to blink every 5 seconds Equipment Profiles EEP F6 04 01 Keycard activation switch Accessories PTM365BP1W Single gang barrier plate for switches UL and CSA certified PTM365BP2W Dual gang barrier plate for switches UL and CSA certified FCC Part 15 231...