ETC Echoflex ELED2 Installation Manual Download Page 5

Page 5

ELED2(H) Installation Guide

Use only UL approved wire when making connections  to the controller, see 

table below.

Controller's Wire Details

Connection 

Color 

Specification

Load 

Red 

14AWG 600V

Neutral 

White

14AWG 600V

Line 

Black 

14AWG 600V

Dimming 0-10V 

Violet and Red

18AWG 600V

Analog Color Control

Violet and Green 18AWG 600V

Dimming GND 

Gray 

18AWG 600V

Linking the First Switch

Use this method to link the first switch. Use the learn button to link additional 

devices.

1.  If the controller already has a sensor linked, press the TEACH button on 

the linked sensor and proceed to step 2 within 60 seconds. 

2.  Click the wireless switch paddle ON three times, OFF three times and 

ON three times sequentially within 5 seconds. The relay will toggle and 

the red POWER LED will begin a repeating blinking pattern to indicate 

the linked switch, see the section on LED blink codes.

 

LEARN button 

The LEARN button is used to link switches or sensors to the controller. 

1.  Press the button marked LEARN for a half second. In link mode the 

LEARN LED will stay ON and the POWER LED will toggle every two 

seconds. The LEDs will be a color that correlates to the channel 

(Red=CH1; Green=Ch2; Blue=Set point). Press the LEARN button to 

scroll through the channels.

2.  When linking a wall switch, press the switch paddle ON three times. 

 

  

 

Tunable White Dimming Controller

Power

LED

Clear

Button

Learn

Button

Learn

LED

Antenna (orange)

Do not cut or cap

   Black - Line, 
   120-277VAC OR
   240-347VAC

@ 50/60 Hz

500 mW max

White - Neutral

Red - Load, switched Hot

Dimming 0-10V Violet and Red

Gray - 

Dimming COM

Tunable White LED fixture

Max. Switching Load

(ELED2) 20A@ 120-277VAC, Electronic Ballast or LED Driver

(ELED2H) 20A@ 240-277VAC Electronic Ballast or LED Driver

(ELED2H) 16A@ 347VAC Electronic Ballast or LED Driver

Max. Dimming Load 100 mA sinking

Max. Impulse Voltage: 4000V    Internal Relay: Type 1.C

Dimming outputs is Class 1 circuit Independently Mounted Control for 

Panel/Surface Mount

Violet with Green stripe   - 

0-10V analog Color control

 

CCT Control Driver

Intensity Control Driver

Neutral to others

Red -  To other LED drivers

(ELED2) 20A@ 120-277VAC, 

Electronic Ballast or LED Driver

(ELED2H) 20A@ 240-277VAC 

Electronic Ballast or LED Driver

16A@ 347VAC Electronic Ballast or 

LED Driver

Dimming COM to others

0-10V Dimming - 100 mA  MAX sinking current

CCT  0-10V  Control - 100 mA MAX sinking current

Violet with Red stripe

Analog Color control

Violet with Green

 

Wiring Diagram

Summary of Contents for Echoflex ELED2

Page 1: ...voltage and should only be in stalled by qualified personnel in accordance with National Electrical Code and any local regulations CAUTION To avoid electrical overload total connected load should not exceed output rating This product is suitable for use in dry locations where the ambient temperature is 5 C to 50 C 23 F to 122 F Do not use outdoors Do not mount near gas or electric heaters Equipmen...

Page 2: ...horized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than its intended use Servicing should be performed by qualified ser vice personnel Pollution Degree 2 ...

Page 3: ...mple Tap technology is included allowing installers and facility operators to manage configuration settings without any specialized tools see wiring diagram on page 5 for detailed output load ratings Preparing To Install The Controller The controller should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel The controller is mounted using t...

Page 4: ...power to the circuit 7 If the controller was pre commissioned you can use one of the pre linked devices to test the controller operation If the controller was not pre commissioned by the factory refer to the section of this guide titled Linking the First Switch Use this switch to verify the controller functionality i Note Always follow applicable NEC and local electrical code requirements when ins...

Page 5: ...ill be a color that correlates to the channel Red CH1 Green Ch2 Blue Set point Press the LEARN button to scroll through the channels 2 When linking a wall switch press the switch paddle ON three times Tunable White Dimming Controller Power LED Clear Button Learn Button Learn LED Antenna orange Do not cut or cap Black Line 120 277VAC OR 240 347VAC 50 60 Hz 500 mW max White Neutral Red Load switched...

Page 6: ...es To return the controller to the factory pre commissioned state press the CLEAR button until the red POWER and green LEARN LEDs start blinking approximately 5 seconds Release the button and the red POWER LED will begin blinking indicating the factory commissioned pre linked devices To completely clear the controller returning it to factory default settings removing all linked devices press the C...

Page 7: ...mber of devices linked This pattern will repeat after a short pause See the ELED2 programming guide for more information https www echoflexsolutions com files 8DC 5884 ELED2 Programming Guide pdf The table below describes the number of LED blinks for each device type Dimming Channel 1 RED POWER LED Blink Codes Factory Default ON Solid switch es 1 long blink followed by short blinks counting switch...

Page 8: ...Std E60730 UL 2043 Plenum rated California Energy Commission Title 24 CEC Washington State Energy Code WSEC ANSI ASHRAE IES Standard 90 1 International Energy Conservation Code IECC New York City Energy Conservation Code NYCECC FCC Part 15 231 Contains FCC ID SZV STM300U IC RSS 210FCC Part 15 231 Contains FCC ID SZV STM300U The enclosed device complies with Part 15 of the FCC Rules Operation is su...

Reviews: