background image

Echoflex Installation Guide

Switch-mount Occupancy Sensor

Station Configuration

The Dual Tech Switch-mount Occupancy Sensor has on-board switch and
button settings that are available from the front of the station when it is
installed and the wall plate is removed.

Program Mode

Press and hold the 

[Walk Test]

 

button 3 seconds to enter Program 
Mode

Function switch
Preset
Custom
Zone

Program Mode

Program Mode allows adjustment of the consecutive range of presets or
zones assigned to the station. Placing the station in Program Mode allows you
to set a new starting preset or zone number for the station.

The programmed preset or zone that is associated to the first button control
is also the event/action that will occur with occupancy and vacancy detection.
Reference

Program Preset Start (Basic Mode, Preset or Zone) on page 13

.

Function switch

The Function switch determines how the controls of the sensor function. It has
behavior settings of Preset, Custom, and Zone.

Function switch: Preset

Setting the Function switch to Preset allows you to perform preset related
actions dependent on the switch-mount sensor type. Reference

Station

Functionality on page 15

for complete details of the button actions when

the switch-mount sensor is placed in Preset mode.

Preset Toggle Functionality

Preset toggle control functionality allows you to toggle the preset on and off
by pushing the assigned preset button.

A single button push activates / deactivates the preset that is assigned
to that button using a two second fade time.

A double button push activates / deactivates the preset that is
assigned to that button using a 1/2 second fade time.

Dual Tech Switch-mount Occupancy Sensor

Page 11 of 20

Echoflex Solutions, Inc.

Summary of Contents for Echoflex Dual Tech

Page 1: ...sensing for lighting control The Dual Tech Switch mount Occupancy Sensor is available in one and two button models and is available with white black cream or gray wall plate Each button is backlit by...

Page 2: ...ambient temperatures of 10 C to 40 C with a maximum of 90 non condensing humidity Installation Echoflex recommends paying special attention to the installation environment When operating in PIR only...

Page 3: ...all Elaho stations and devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Categ...

Page 4: ...ed in the termination kit and the incoming ground wire b Use one WAGO connector provided in the termination kit to connect the sensor ESD ground pigtail and the incoming ground For sensors using groun...

Page 5: ...s 1 Commands are shared by all devices within n assigned space 1 Set the Space rotary switch to the desired number 1 through 16 for the space you want the sensor to control 2 Set the Address rotary sw...

Page 6: ...l be disabled Only blue LEDs will illuminate When set to Off default the amber button LEDs on the station are enabled Amber LEDs are provided as the default so the station glows in darkened spaces all...

Page 7: ...ensors ship with standard button legends installed beneath a clear lens Note Customize and print your own button legends on standard transparency Download the button legend template provided on the Ec...

Page 8: ...nto the switch box To install multiple stations multi gang insert the station electronics into the box from the right to the left side for the best alignment and fit The alignment bracket will slightl...

Page 9: ...screws then retry wall plate installation Power Up and Test Power Up All EchoConnect terminations in the system must be made before applying power to the system and sensor When the sensor is powered...

Page 10: ...tem b You will need direct access to the sensor in order to place it into Walk Test mode 2 Remove the sensor wall plate to gain access to the Walk Test button 3 Press the Walk Test button on the top r...

Page 11: ...tion Reference Program Preset Start Basic Mode Preset or Zone on page 13 Function switch The Function switch determines how the controls of the sensor function It has behavior settings of Preset Custo...

Page 12: ...features either with or without ElahoAccess although the presence of ElahoAccess in the control system allows for an expanded feature set With ElahoAccess ElahoAccess provides complete customization o...

Page 13: ...he station Function switch to its highest position of Preset 2 Press and hold the Walk Test Program Mode button for three seconds to enter Program Mode The Mode LED illuminates steady amber and the fi...

Page 14: ...ush button 1 to increase the starting zone number by one any new count always begins at 1 The station will update the LED indication flashing the LED to reflect the new zone number For example pushing...

Page 15: ...r switches are set to Off Reference page 5 With the Function switch set to Preset Preset 1 is the default With the Function switch set to Zone Zone 1 is the default With the Function switch set to Cus...

Page 16: ...s Double tap the button to toggle the preset using a 1 2 second fade time Custom While the one button switch mount sensor supports the following default button actions in Custom mode complete customiz...

Page 17: ...dress 1 Space 1 Reference Rotary and DIP Switches on page 5 DIP switches 1 4 and 5 are set to On All other switches are set to Off Reference page 5 With the Function switch set to Preset Preset 1 is t...

Page 18: ...P Switches on page 5 for instructions to change this default setting Zone In Zone mode an occupancy detection event activates the zone that is configured to button 1 at full and the vacancy detection...

Page 19: ...activates the zone that is configured to button 1 at full and the vacancy detection event deactivates the Zone set to 0 Double tap the button to toggle the preset using a 1 2 second fade time Note The...

Page 20: ...lation Guide Switch mount Occupancy Sensor Sensor Coverage 14 m 45 ft 14 m 45 ft 14 m 45 ft 15 180 9 m 30 ft 9 m 30 ft Top View Side View Dual Tech Switch mount Occupancy Sensor Page 20 of 20 Echoflex...