ETC Setup Guide
EBDK Reset Switch
EBDK Reset Switch
Page 2 of 3
ETC
Install EBDK Reset Switch for an EBDK
1:
Install the back box according to standard electrical practices. The back box should be installed flush
and square for best installation results.
2:
Pull two 1.5 mm
2
(16 AWG) wires through grounded metal conduit from the EBDK to the installed
single-gang back box.
3:
Strip 9-10 mm (3/8 in) from the ends of the 1.5 mm
2
(16 AWG) installed control wires.
4:
Locate the WAGO cage clamp connectors in the packaging. WAGO connectors are provided as a
means to connect the installed control wire to the harness wires provided on the EBDK-SWITCH.
5:
Open two terminal levers on each WAGO connector and insert the 1.5 mm
2
(16 AWG) installed
control wire for V out and the Input switch wire into terminals and close the levers. See the image
below for topology.
6:
Install the switch into the back box and secure using the two screws provided.
Note:
You can wire up to two EBDK Reset Switches in series within a maximum distance of
152 m (500 ft) between the EBDK and the last EBDK-SWITCH in the line.
Note:
You can install up to two EBDK Reset Switches in series per EBDK (see image below).
EBDK
EBDK Reset Switch
EBDK
EBDK Reset Switch
EBDK Reset Switch
Two
switches
in series
Single
switch