ETC E-DOC-C-HC Installation Manual Download Page 3

Echoflex Installation Guide

Dual Tech Occupancy Sensor

Wire Specification

The Dual Tech Occupancy Sensor connects to the EchoConnect
communication bus. EchoConnect is a bi-directional protocol that uses one
pair of wires (data + and data -) for both data and power. Echoflex
recommends using Belden 8471 Class 2 wire (or approved equal - see the
Echoflex cable cross database

echoflexsolutions.com/files/Elaho_Data_Cable_

Wire_Specs

for equal alternatives). The total combined length of an

EchoConnect wire run using Belden 8471 may not exceed 500 m (1,640 ft),
with a maximum distance of 400 m (1,312 ft) between any two devices.

Note:

All control wiring should be installed and terminated by a

qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4 cm (10 in) of wiring in the back
box for connection and to allow slack for future service needs.

Note:

Echoflex requires that all stations and devices be grounded for

ESD protection. Pull an additional 2.5 mm

2

(14 AWG) wire for

grounding when control wires are not installed in grounded metal
conduit.

Note:

When using Category 5 (or equivalent) cable on the

EchoConnect communication bus, please note the following:

Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (8186A1207) for information to terminate
Cat5 wiring.

Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.

Supplies

The following supplies are provided with the sensor:

Soft ceiling tile adapters

2 each mounting screws, 6-32 x 3/4" and 6-32 x 1 3/4"

Lens masks

WAGO connectors, 3-position

Dual Tech Occupancy Sensor

Page 3 of 12

Echoflex

Summary of Contents for E-DOC-C-HC

Page 1: ...ens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m 2 Coverage ft 2 E DOC C SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7 m 800 ft 2...

Page 2: ...environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sens...

Page 3: ...ck box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for groundi...

Page 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Page 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Page 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Page 7: ...t to On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Swit...

Page 8: ...ot allowed and no events are triggered Configuration Basic MODE button and LED AUXILIARY button and LED A sensor that is set for Basic configuration mode DIP switch 2 set to Off can be further configu...

Page 9: ...the preset used 3 Press and release the MODE button to save the current setting Operation Dual Technology When both PIR and acoustic detection are used the following logic is used When the space is va...

Page 10: ...riod The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or restore the previous lighting condition Aut...

Page 11: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Page 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...