Common Tasks
33
Other Panic Settings
In the Panic Setup menu ([Setup]>Panic) you can configure the following panic settings:
• In Delay (sec): Length of time (in seconds) for the panic look to delay before activating (default
is 0)
• Out Delay (sec): Length of time (in seconds) for the panic look to delay before deactivating
(default is 0). To require manual intervention to turn off panic from the face panel or via ACN,
press [Last] when Out Delay is set to 0 or use the scroll wheel to select Man.
• Fade In (sec): Length of time (in seconds) for the panic look to fade in when activated (default is 2)
• Fade Out (sec): Length of time (in seconds) for the panic look to fade out when deactivated
(default is 2)
• Shed Other Loads: This Yes/No setting determines if active levels at the moment of the panic
trigger should remain active or be forced off. Default is N (No).
The following image illustrates how these settings affect panic function.
Level
Time
Panic
Activated
Panic
Deactivated
In Delay
0–360s
Fade In
0–360s
Out Delay
0–360s
Fade Out
0–360s
Steady State
until contact changes
Indicator turns on
Indicator turns off
Panic Levels
Off
Panic Fade Diagram