ETC Installation Guide
SC1008 BCELTS
SC1008 BCELTS
Page 6 of 11
ETC
Dimmed or Switched Load
The SC1008 has the ability to separate the sensing of normal power from the load itself; this allows
you to have a light switch or dimmer controlling the load when normal power is available, but to
have the load transfer to emergency power in the event of normal power loss.
The SC1008 can be used with a line voltage switch or dimmed power control.
SENSE
L
O
AD
NORM
AL
EMER
GENC
Y
H
2
N
4
H
5
N
6
H
7
N
3
1
H
8
N
dimmer
or
switch
Emergency
power panel
Normal power
panel
Load
see step 3 note
1. See
Wire and Terminal Specifications on page 4
for wire size, strip length, and terminal
torque.
2. Terminate load wires.
a. Run a neutral and a hot load wire through conduit for the load to be transferred from the
SC1008 to the load position.
b. Terminate to the respective terminals LOAD 2N (neutral) and LOAD 1H (hot) in the
SC1008 enclosure, securing each terminal screw onto the wire.
3. Install a jumper wire (included) between SENSE 4N (neutral) and Normal 6N (neutral).
Note:
If using a separate neutral for the sense circuit, do not install the jumper. If using a
three-wire feed as shown above, install the jumper as described in step 3.
4. Terminate normal power wires.
a. Run a neutral and a hot wire through conduit from the normal power source (controlled
dimmer or switch) to the SC1008.
b. Terminate the neutral wire to the NORMAL 6N (neutral) terminal and secure the terminal
screw onto the wire and the jumper fork terminal.
c. Terminate the hot wire to the NORMAL 5H (hot) terminal and secure the terminal screw
onto the wire.
5. Terminate normal sense wire.
a. Run a hot sense wire from a non–controlled output of the normal power source through
conduit to the SC1008.
b. Terminate to SENSE 3H (hot) in the SC1008 enclosure, securing the terminal screw onto
the wire.
6. Terminate emergency power wires.
a. Run a neutral and a hot wire through conduit from the emergency power
source to the SC1008.
b. Terminate to the respective terminals EMERGENCY 7N (neutral) and
EMERGENCY 6H (hot) in the SC1008 enclosure, securing each terminal screw onto the
wire.