ArcLamp System Installation Manual
Terminate Maintained (Emergency) Input
ArcLamp Emergency Driver 150
ArcLamp Emergency Driver 150
Sense and Maintained Input Detail
Factory Wire Colors
Model
Color
Type
North
America
and Europe
green/yellow
ground/earth
North
America
black
line/hot
North
America
white
neutral
Europe
brown
live
Europe
blue
neutral
1. See
Wire and Terminal Specifications on page 16
for specification of wire, strip length,
and terminal torque ratings. Prepare the wires accordingly.
2. Run ground, neutral, and line (hot) wires between the ArcLamp Emergency Driver
Maintained input terminals and an emergency branch circuit with an upstream UL1008
automatic transfer switch.
a. Terminate the ground wire (typically green/yellow) to the ground screw provided.
•
Loosen the ground screw, insert the pre-stripped emergency ground wire, and
tighten the screw firmly to secure both wires in place.
b. Terminate emergency neutral and line (hot) wires to the Maintained input terminals.
•
Insert the neutral wire (typically white) into the Maintained N terminal and
tighten the screw firmly to secure it in place.
•
Insert the line (hot) wire into the Maintained L terminal and tighten the screw
firmly to secure it in place.