22

ArcLamp System Installation Manual

Bridging Output Channels

It is acceptable to bridge multiple output channels together, ganging the maximum output
allowed into a single combined output channel. See

Bridge Output Channels on page 37

for

examples of the configurations made possible by bridging output channels.

For example, bridging all four output channels on an ArcLamp Driver 350 or two channels on an
ArcLamp Driver 700 creates a single bridged output channel that can support 60 ArcLamps. 60
ArcLamps on a bridged channel draw about 8 A, allowing the single bridged channel to support
the large number of ArcLamps.

Note:

This installation technique reduces the number of available output channels.

See

Bridge Output Channels on page 37

.

Note:

A maximum of two output channels can be bridged together on an

ArcLamp Driver 700 (standard or emergency model).

For more information, see

Bridge Output Channels on page 37

.

DMX In and DMX Thru

DMX In and DMX Thru cables terminate to RJ45 connectors (all models) or to eight-pin
connectors (ArcLamp Driver 350 and 700 standard and emergency models). DMX is installed in
a daisy chain topology and includes one pair of wires (data +, data -) plus an ISO ground
(common).

RJ45 Pinout Information

Pin

Description

1

Data +

2

Data -

7&8

ISO ground
(common)

RJ45 DMX Termination

All models of ArcLamp Driver have RJ45 receptacles for
DMX In and Thru.

ETC recommends Cat5e (or better) minimum 0.2 mm

2

(24 AWG) conductors terminated to T568B standard. The
DMX In and Thru RJ45 connectors on the wall-mount
ArcLamp Driver 350 and 700 are not labeled and are
interchangeable. Their locations are shown below.

Summary of Contents for ArcLamp 150 Systems

Page 1: ...ArcLamp System Installation Manual Part Number 7490M2130 Rev E Released 2020 12 ...

Page 2: ...rademarks and patents go to etcconnect com ip All other trademarks both marked and not marked are the property of their respective owners ETC intends this document whether printed or electronic to be provided in its entirety ...

Page 3: ...on Location 12 ArcLamp Drivers 12 Power Disconnect Device 12 ArcLamp Installation 13 ArcLamp Voltage Drop 14 Maximum Distance Between ArcLamp Driver and Fixture with ArcLamps Installed 14 Chapter 3 Wall Mount Driver Installation 15 Electrical and Wiring Specification 15 Wire and Terminal Specifications 16 Prepare for Wall Mount Installation 16 Wall Mounting Supplies 16 Wall Mount the Driver 17 Ter...

Page 4: ...enna 30 TX1 Transmitter 30 Power Up Procedure 30 Updating the Driver Firmware 31 Wireless ArcMesh Luminaires 31 RDM Luminaires 31 ArcLamp with ArcMesh Configuration and Commissioning 31 ArcLamp RDM Configuration 31 Maintenance 33 Troubleshooting 34 LED Indicators 34 Overload Protection 35 Fade to Warm Behavior 36 Appendix A Bridge Output Channels 37 Voltage Drop 38 Wall Mount Bridging Kits 39 Rack...

Page 5: ...rgency Operation and Test 56 Appendix D TX1 Installation 57 Preparing for Installation 58 Supplies 58 Electrical and Wiring Specifications 58 Mounting 58 Terminate Wiring 59 Power 60 DMX In and DMX Out 60 DMX Cable Preparation and Termination 61 DMX Wire Termination 62 Auxiliary Input 63 Final Installation and Power Up 63 Front Panel LEDs 63 Attach Antenna 64 Dual Redundancy Operation 64 Maintenan...

Page 6: ...iv ArcLamp System Installation Manual ...

Page 7: ...ent uses the following conventions to draw your attention to important information Note Notes are helpful hints and information that is supplemental to the main text CAUTION A Caution statement indicates situations where there may be undefined or unwanted consequences of an action potential for data loss or an equipment problem WARNING A Warning statement indicates situations where damage may occu...

Page 8: ...umber if you have called in previously Americas United Kingdom ETC Inc ETC Ltd Technical Services Department Technical Services Department 3031 Pleasant View Road 26 28 Victoria Industrial Estate Middleton WI 53562 Victoria Road 800 775 4382 USA toll free London W3 6UU England 1 608 831 4116 44 0 20 8896 1000 service etcconnect com techservltd etcconnect com Asia Germany ETC Asia ETC GmbH Technica...

Page 9: ...s should always be followed including the following READ AND FOLLOW ALL SAFETY INSTRUCTIONS Do not use outdoors Do not let power supply cords touch hot surfaces Do not mount near gas or electric heaters Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufactu...

Page 10: ...naires eliminating the need for invasive rewiring ArcLamp is an LED source that is available in several models including the choice of screw base color temperature and clear or frosted glass finish ArcLamp is designed to be the energy efficient solution for chandeliers sconces wall lights proscenium lights and more The DMX controlled ArcLamp Driver includes onboard device management with up to fou...

Page 11: ...ARCLRDMRE350 with RDM Supports 60 total 4 4 W ArcLamps 15 per channel Max current per channel 3 A Max power per channel 72 W ArcLamp 700 Systems Features Standard Wall Mount ARCLMD700CV24 with ArcMesh ARCLRDMD700CV24 with RDM Standard Rack Mount ARCLMDR700 with ArcMesh ARCLRDMR700 with RDM Emergency Wall Mount ARCLMDE700CV24 with ArcMesh ARCLRDMDE700CV24 with RDM Emergency Rack Mount ARCLMDRE700 w...

Page 12: ...ims available in CCT 2700 K standard and FTW or 3000 K standard only versions low voltage 24 VDC operation powered and controlled from an ArcLamp Driver dimmable from 0 to 100 silent operation ArcLamp LED lamps install directly to fixtures compatible with standard medium screw style E26 or E27 and candelabra style E12 or E14 bases A C A B B D E F A Globe Style D E12 or E14 candelabra style base B ...

Page 13: ...able for systems requiring emergency lighting control Each fixture with ArcLamps installed can be configured to be UL924 listed when wired to an existing emergency response system ArcLamp drivers are available in RDM models which control an ArcLamp System with wired DMX RDM or models with wireless capability that control an ArcLamp System using ArcMesh wireless protocol Wall Mount ArcLamp Driver 7...

Page 14: ...river 150 ArcLamp Driver 350 wall mount single fan ArcLamp Emergency Driver 350 ArcLamp Driver 350 rack mount single fan ArcLamp Emergency Driver 350 ArcLamp Driver 700 wall mount dual fans ArcLamp Emergency Driver 700 ArcLamp Driver 700 rack mount dual fans ArcLamp Emergency Driver 700 Channel Electrical Specifications Driver Description Maximum Current per Channel Maximum Power per Channel Maxim...

Page 15: ...with Class 1 control circuits in the NEC Class 1 circuits are permitted to be installed with other power circuits that are functionally associated 725 48 B 1 Class 1 circuits and power supply circuits shall be permitted to occupy the same cable enclosure or raceway only where the equipment powered is functionally associated Following these NEC specifications for renovation installations ArcLamp ci...

Page 16: ...phic shows a basic hybrid ArcLamp system installation with a wireless ArcLamp driver ArcLamps transmitter and a wired DMX console for the main control source ArcLamp systems are compliant with DMX 512 A ANSI E1 11 2008 R2013 DMX loss behavior is hold last look wiring between luminaire and power supply TX1 Transmitter ArcLamp Driver with wireless ArcMesh ArcLamps in existing fixture ArcMesh wireles...

Page 17: ...ll this kit only in the luminaires that have the construction features and dimensions shown in the photographs and or drawings Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation AVERTISSEMENT RISQUE DE CHOC ÉLECTRIQUE Risque d incendie ou de choc électrique Installez ce kit uniquement dans des luminaires qui ont les caractéristiques de co...

Page 18: ...e input power disconnect device installed ahead of your ArcLamp driver WARNING RISK OF DEATH BY ELECTRIC SHOCK Failure to disconnect all power to the system before installation maintenance cleaning or any other system modification could result in serious injury or death AVERTISSEMENT RISQUE DE MORT PAR DÉCHARGE ÉLECTRIQUE Négliger de débrancher toutes les sources d alimentation du système avant l ...

Page 19: ...Note The fixture and its installation location must support the ArcLamp Note The number of designated emergency lamps and their height is the responsibility of the specifier and installer in order to achieve the minimum FC levels of NFPA101 Other installation scenarios should be evaluated by the AHJ to confirm illuminance and performance requirements of ANSI NFPA and the IBC The LED driver has bee...

Page 20: ...nce between the ArcLamp driver and ArcLamp based on using each driver at its maximum rated capacity These distances will be reduced when bridging driver output channels together see Bridge Output Channels on page 37 Maximum distances depend on wire gauge See recommended wire gauges at Wall Mount Driver Installation on page 15 for wall mount models and Rack Mount Driver Installation on page 25 for ...

Page 21: ...ible power disconnect device cannot be serviced or operated safely AVERTISSEMENT Il est imprudent d utiliser ou de réparer les circuits installés sans qu un dispositif de déconnexion de l alimentation ne soit accessible Install the ArcLamp Driver on a power distribution system with reliably identified earthed neutral and install a maximum 15 A circuit breaker on the line conductor ETC recommends i...

Page 22: ...erminate the last driver in line with a DMX terminator plug in the RJ45 Thru receptacle See RJ45 DMX Termination on page 22 DMX In Thru Eight pin Connector ArcLamp Driver 350 and 700 standard and emergency models Belden 9729 or equivalent A 120Ω resistor not provided is required to terminate the last DMX device in a control run See DMX Cable Preparation and Termination on page 23 Refer to Channel ...

Page 23: ...nch holes as needed for conduit for power connection and data connection Reinstall the removable panel to the backbox Note Make sure that the flexible electrical supply can extend through the ceiling opening so that the driver and luminaire can be inspected and serviced when needed Note Use suitable conduit where required by national and local codes Note Drivers may require additional means of sec...

Page 24: ...50 Wall Mount ArcLamp Driver 350 Wall Mount ArcLamp Driver 700 Wall Mount E C A B D E A Power input B Output channels C Antenna D DMX input and thru RJ45 E DMX input and thru eight pin terminal blocks The antenna is not present on RDM models Eight pin terminal blocks are not present on ArcLamp Driver 150 ...

Page 25: ...er wiring should only be installed and terminated by a qualified electrician and should follow standard wiring installation practices 1 Make sure power is off at the main circuit breaker 2 See Wire and Terminal Specifications on page 16 for specification of wire strip length and terminal torque ratings Prepare the wires accordingly 3 Loosen the three screw terminals for NEUTRAL N GROUND and LINE L...

Page 26: ...rminal B tool slot square To install wire insert the wire into the terminal To remove wire insert a 3 5 mm flatblade screwdriver into the tool slot next to the wire terminal to release the wire then pull the wire out of the terminal Wall Mount ArcLamp Driver 350 and 700 Power Input Detail Factory Wire Colors Model Color Type North America and Europe green yellow ground earth North America black li...

Page 27: ...d fixture are terminated to output terminals on the ArcLamp Driver Termination is available for up to four uniquely addressable outputs channels Note Power wiring should only be installed and terminated by a qualified electrician and should follow standard wiring installation practices 1 Make sure power is off at the main circuit breaker 2 See Wire and Terminal Specifications on page 16 for specif...

Page 28: ...Bridge Output Channels on page 37 Note A maximum of two output channels can be bridged together on an ArcLamp Driver 700 standard or emergency model For more information see Bridge Output Channels on page 37 DMX In and DMX Thru DMX In and DMX Thru cables terminate to RJ45 connectors all models or to eight pin connectors ArcLamp Driver 350 and 700 standard and emergency models DMX is installed in a...

Page 29: ...representative and request part number N4086 Eight Pin DMX Termination ArcLamp Driver 350 and 700 standard and emergency models have eight pin headers for DMX In and Thru in addition to the RJ45 receptacles described in the previous section Note Total length of Belden 9729 should not exceed 500 m 1640 ft between the control source and the ArcLamp Driver Eight Pin Connector Pinout Pin Description 1...

Page 30: ...e pair twist as close to the screw terminal connector as possible and terminate the wires Insert the data wire typically black into the terminal labeled DMX and secure Insert the data wire typically red or white into the terminal labeled DMX and secure Insert the common shield wire into the terminal labeled DMX and secure 11 Bend back the unused set of wires and secure them to the cable with a wir...

Page 31: ... access with the use of a key If this equipment is installed in a location without restricted access the wiring area of the rack should only be accessible with the use of a tool Electrical and Wiring Specification WARNING Circuits that are installed without an accessible power disconnect device cannot be serviced or operated safely AVERTISSEMENT Il est imprudent d utiliser ou de réparer les circui...

Page 32: ... location where it will not readily be subjected to tampering by unauthorized personnel Elevated Operating Ambient If the ArcLamp Driver is installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may elevate avoe the room ambient Do not operate the device in an enclosed environment above 40 C 104 F Reduced Air Flow When installing the ArcLamp Dri...

Page 33: ...B C D E F G Rack Mount ArcLamp Driver 700 A Output channel CH 1 E DMX In B Output channel CH 2 F DMX Thru C Output channel CH 3 G Power input D Output channel CH 4 Power Input Wiring 1 Ensure power to the rack is off 2 Connect the AC input to the AC power source using the provided power input cord ...

Page 34: ... on the provided two position screw terminal plug c Terminate the neutral wire to the terminal securing the terminal screw onto the wire d Terminate the line hot wire to the terminal securing each terminal screw onto the wire e Tug gently on the wires to ensure they are secure Bridging Output Channels It is acceptable to bridge multiple output channels together ganging the maximum output allowed i...

Page 35: ...f wires data data plus an ISO ground common Terminate DMX In and Thru ETC recommends Cat5e or better minimum 0 2 mm2 24 AWG conductors terminated to T568B standard Note ArcLamp drivers are not self terminating You must terminate the last driver in line with a DMX terminator plug in the RJ45 Thru receptacle To purchase an RJ45 terminator please contact your ETC customer service representative and r...

Page 36: ...e réparer les circuits installés sans qu un dispositif de déconnexion de l alimentation ne soit accessible Note Read this section completely before powering up the system 1 Verify that all fixtures to be powered by the ArcLamp Driver have ArcLamps installed and the provided caution label has been installed on the fixture for future lamp replacement reference 2 Check the DMX control source to ensur...

Page 37: ... free at etcconnect com When commissioning a system installation check all ArcSystem drivers and multi cell luminaires to ensure that the latest firmware is present If the firmware is not up to date upgrade it using ETC Concert and ETC UpdaterAtor software before commissioning is completed For more information on UpdaterAtor download the UpdaterAtor Software Quick Guide for free at etcconnect com ...

Page 38: ...ressing Set to 1 sets DMX personality to multi channel Set to 2 sets DMX personality to single channel Identify Device 0x1000 0 for stop identify 1 for start identify Set causes to 1 causes the outputs and LEDs of the unit to blink in a one second on one second off pattern Minimum Level 0x0341 0 to 255 Default is 99 The driver will not accept a Minimum Level that is higher than the Maximum Level M...

Page 39: ...orking Practices WARNING Circuits that are installed without an accessible power disconnect device cannot be serviced or operated safely AVERTISSEMENT Il est imprudent d utiliser ou de réparer les circuits installés sans qu un dispositif de déconnexion de l alimentation ne soit accessible ArcLamps Inspect the ArcLamps for dust As needed use a lint free cloth to wipe the lamps ArcLamp Driver Inspec...

Page 40: ... changing Solid On wireless operation active DMX signal is being received Solid On wired DMX DMX is present Status Steady blinking processor is operating normally Solid On system is responding to DMX instruction Solid On when no DMX command is being sent there is a processor fault Contact ETC Technical Services for assistance Channel OK LEDs Solid On with no Channel Limit LEDs lit channel is outpu...

Page 41: ...s will turn off and Channel OK LEDs will turn solid on when the circuit reconnects Warning Limits and Trip Limits Driver Description Warning Limits Trip Limits Single Channel Number of Channels Per Bridge Single Channel Number of Channels Per Bridge 2 3 4 2 3 4 ArcLamp Driver 150 or ArcLamp Emergency Driver 150 NO WARNING OR TRIP LEDs If circuits are overloaded on an ArcLamp Driver 150 output may ...

Page 42: ...o warm behavior ArcLamp systems with ArcMesh must have Fade to Warm Inhibit unchecked in ArcSystem commissioning software at the time of initial system setup ArcLamp systems with RDM must have the ArcLamp Enable FTW Support parameter set to true See ArcLamp Enable FTW Support on page 32 ...

Page 43: ...cabinet or other readily accessible input power disconnect device for the normal power input and emergency power input when used is locked out and tagged out AVERTISSEMENT RISQUE DE MORT PAR DÉCHARGE ÉLECTRIQUE Avant de passer le câblage et de le raccorder au boîtier du driver ArcLamp ou à l émetteur TX1 s assurer de la coupure électrique du disjoncteur principal ou d une autre arrivée électrique ...

Page 44: ... than the calculated ideal which allows more ArcLamps to be driven by a single bridged channel than you might expect from calculations Note All output channels have on board overload protection See Overload Protection on page 35 Note The installation site must consider power requirements at the fixture and allow for voltage drop with distance See Voltage Drop below Voltage Drop Correct operation o...

Page 45: ...ne 5 position WAGO connector with four attached black wires terminated with forks 3 7490K2004 bridging kit for ArcLamp Driver 700 or ArcLamp Emergency Driver 700 for bridging combinations of 2 channels two 3 position WAGO connectors each with two attached black wires terminated with forks Rack Mount Bridging Kits 1 7490K2005 bridging kit for rack mount ArcLamp Driver 350 for bridging combinations ...

Page 46: ... Mount ArcLamp Driver 700 S1 S2 S3 S4 CH 1 CH 2 CH 3 CH 4 S1 S2 S3 S4 Switch blocks Rack Mount ArcLamp Driver 350 Rack Mount ArcLamp Driver 700 Switch Blocks Each of the four switch blocks controls one output channel Switch block S1 controls the output channel labeled LED OUT 1 on ArcLamp Driver 150 or CH 4 on ArcLamp Driver 350 and 700 Switch block S2 controls the output channel labeled LED OUT 2...

Page 47: ...dividual Output Channel Control Switch Block Output Switch Positions 1 2 3 4 5 6 S4 CH 1 Do not adjust from factory setting ON OFF OFF OFF Do not adjust from factory setting S3 CH 2 OFF ON OFF OFF S2 CH 3 OFF OFF ON OFF S1 CH 4 OFF OFF OFF ON Setting Switches 2 Through 5 for Bridged Output Channels Note Each output channel that you want to bridge must have the same setting for switch positions 2 5...

Page 48: ... 350 Rack Mount ArcLamp Driver 350 Note Do not bridge three or four output channels into one output channel on an ArcLamp Driver 700 ArcLamp Driver 150 Switch Settings for Four Output Channels Bridged into One Switch Block Output Switch Positions 1 2 3 4 5 6 S1 LED OUT 1 Do not adjust from factory setting ON OFF OFF OFF Do not adjust from factory setting S2 LED OUT 2 ON OFF OFF OFF S3 LED OUT 3 ON...

Page 49: ...ONN5 CONN6 CONN8 CONN9 CH1 CH2 CH3 CH4 ArcLamp Driver 150 Wall Mount ArcLamp Driver 350 Wall Mount ArcLamp Driver 700 Rack Mount ArcLamp Driver 350 Rack Mount ArcLamp Driver 700 ArcLamp Driver 150 Switch Settings for Output Channels Bridged in Pairs Switch Block Output Switch Positions 1 2 3 4 5 6 S1 LED OUT 1 Do not adjust from factory setting ON OFF OFF OFF Do not adjust from factory setting S2 ...

Page 50: ...H1 CH2 CH3 CH4 ArcLamp Driver 150 Wall Mount ArcLamp Driver 350 Rack Mount ArcLamp Driver 350 Note Do not bridge three or four output channels into one output channel on an ArcLamp Driver 700 ArcLamp Driver 150 Switch Settings for Three Output Channels Bridged into One Switch Block Output Switch Positions 1 2 3 4 5 6 S1 LED OUT 1 Do not adjust from factory setting ON OFF OFF OFF Do not adjust from...

Page 51: ...ol Switches on page 40 e Replace the cover on the rack mount ArcLamp Driver and reinstall the driver in the equipment rack 2 Choose a WAGO connector from the bridging kit with at least one more position than the number of channels to be bridged 3 Bus the negative poles of the output channel connectors Output channels are labeled LED OUT 1 LED OUT 2 LED OUT 3 and LED OUT 4 on ArcLamp Driver 150 or ...

Page 52: ...50 Rack Mount ArcLamp Emergency Driver 700 ArcLamp Emergency Drivers are available for systems requiring emergency lighting control Each fixture with ArcLamps installed can be configured to be UL924 listed when wired to an existing emergency response system Note Fixtures with ArcLamps installed must be hard wired to an ArcLamp Emergency Driver to be considered for UL924 certification The installat...

Page 53: ...y Drivers require two branch circuit power input connections normal sense and maintained emergency Maintained emergency provides constant power to the ArcLamp Driver regardless of the state enforcing the ability to maintain a lights on condition when needed The power source must be connected to an emergency branch circuit with an upstream UL1008 automatic transfer switch Normal sense detects when ...

Page 54: ...Emergency Driver 350 Wall Mount ArcLamp Emergency Driver 700 F B B A C E D F B A Maintain emergency power input B Sense normal sense power input C Output channels D Antenna E DMX input and thru RJ45 F DMX input and thru eight pin terminal blocks The antenna is not present on RDM models Eight pin terminal blocks are not present on 150 W models ...

Page 55: ...ension avant d ouvrir With the exception of power input terminations Wall Mount ArcLamp Emergency Driver installation requirements are the same as those of the standard Wall Mount ArcLamp Driver Complete the installation as follows referencing these sections for installation details Review Prepare for Wall Mount Installation on page 16 Review Electrical and Wiring Specification on page 15 Complete...

Page 56: ...und earth North America black line hot North America white neutral Europe brown live Europe blue neutral 1 See Wire and Terminal Specifications on page 16 for specification of wire strip length and terminal torque ratings Prepare the wires accordingly 2 Run ground neutral and line hot wires between the ArcLamp Emergency Driver Sense input terminals and a normal power branch circuit a Terminate the...

Page 57: ...ncy Driver 350 700 Sense Input Detail Factory Wire Colors Model Color Type North America and Europe green yellow ground earth North America black line hot North America white neutral Europe brown live Europe blue neutral 1 Make sure power is off at the main circuit breaker 2 See Wire and Terminal Specifications on page 16 for specification of wire size and strip length Prepare the wires accordingl...

Page 58: ...n ground neutral and line hot wires between the ArcLamp Emergency Driver Maintained input terminals and an emergency branch circuit with an upstream UL1008 automatic transfer switch a Terminate the ground wire typically green yellow to the ground screw provided Loosen the ground screw insert the pre stripped emergency ground wire and tighten the screw firmly to secure both wires in place b Termina...

Page 59: ...350 700 Sense and Maintained Input Detail Factory Wire Colors Model Color Type North America and Europe green yellow ground earth North America black line hot North America white neutral Europe brown live Europe blue neutral 1 Make sure power is off at the main circuit breaker 2 See Wire and Terminal Specifications on page 16 for specification of wire size and strip length Prepare the wires accord...

Page 60: ... de passer le câblage et de le raccorder au boîtier du driver ArcLamp ou à l émetteur TX1 s assurer de la coupure électrique du disjoncteur principal ou d une autre arrivée électrique pour l alimentation normale et l alimentation de secours lorsqu elle est utilisée s assurer aussi que le disjoncteur ou le dispositif de déconnexion est verrouillé et identifié Rack mount ArcLamp Emergency Drivers so...

Page 61: ... to the normal sense AC power source using the provided power input cord Connect the Maintained Emergency input to the maintained emergency AC power source using the provided power input cord Complete Output Wiring to Fixture on page 28 Complete DMX In and DMX Thru on page 29 After completing ArcLamp Emergency Driver installation see Final Installation and Operation on page 30 ...

Page 62: ...stème peut causer des blessures graves ou la mort De energize main feed to ArcSystem ArcLamp and follow appropriate Lockout Tagout procedures as mandated by NFPA 70E It is important to note that electrical equipment such as breaker panels can present an arc flash hazard if improperly serviced This is due to the high amounts of short circuit current available on the electrical supply to this equipm...

Page 63: ...corder à l émetteur TX1 s assurer de la coupure électrique du disjoncteur principal ou d une autre arrivée électrique pour l alimentation normale et l alimentation de secours lorsqu elle est utilisée s assurer aussi que le disjoncteur ou le dispositif de déconnexion est verrouillé et identifié WARNING Circuits that are installed without an accessible power disconnect device cannot be serviced or o...

Page 64: ...und in conduit up to 10 AWG solid or stranded up to 6 mm2 7 mm 1 4 in 0 5 Nm 4 in lb AUX contact inputs input 1 input 2 ground in conduit 22 14 AWG solid or stranded 0 6 1 6 mm2 5 mm 3 16 in 0 5 Nm 4 in lb DMX in out terminals in conduit Belden 9729 or equivalent See Terminate Wiring on the facing page Mounting The TX1 Transmitter can be set on a flat horizontal surface such as a table top or surf...

Page 65: ...tion 59 Terminate Wiring GND DATA DATA GND DATA DATA DMX IN DMX OUT GND AUX contact Inputs ground is common for both inputs Power Terminals front panel LEDs I P 2 I P 1 Fuse NEUTRAL N GROUND HOT L Fuse 250V 1 25A T ...

Page 66: ...ccordingly 3 Loosen the three screw terminals for NEUTRAL N GROUND and LINE L connections 4 Insert the ground wire typically green into the GROUND terminal and tighten the screw 5 Insert the neutral wire typically white into the NEUTRAL N terminal and tighten the screw 6 Connect the hot wire typically black into the HOT L terminal and tighten the screw 7 Tug gently on the wires to ensure they are ...

Page 67: ...f TX1 Transmitter with DMX IN connected See DMX Cable Preparation and Termination on page 23 DMX Cable Preparation and Termination This instruction assumes preparation of Belden 9729 or equivalent cable for termination to the three position screw terminal connector provided Note Not for use with Cat5 Cat5e or Cat6 cable When running DMX with these cable types use the 3 position IDC connector ...

Page 68: ...the wire pair twist as close to the screw terminal connector as possible and terminate the wires Insert the data wire typically black into the terminal labeled DMX and secure Insert the data wire typically red or white into the terminal labeled DMX and secure Insert the common shield wire into the terminal labeled DMX and secure 11 Bend back the unused set of wires and secure them to the cable wit...

Page 69: ...gs Prepare the wires accordingly 3 Terminate ground and auxiliary contact wires to the auxiliary input terminals a Install the ground common wire typically green yellow to the GND terminal and secure the screw onto the wire If your system requires two auxiliary contact inputs the ground terminal will accept both wires b Install the auxiliary input wire to the I P 1 terminal and secure the screw on...

Page 70: ...ible to daisy chain DMX through the TX1 transmitters because they have active outputs Note DMX Out is a regenerated data output signal and not a passive through Only the DMX channels that are patched to the 64 ArcSystem channels are available on the DMX Out port When two transmitters are used on the same wireless network ID radio channel the system will determine a master transmitter and a backup ...

Page 71: ...se limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cau...

Page 72: ... 683 Hong Kong 852 2799 1220 Paris FR 33 1 4243 3535 Web etcconnect com Support support etcconnect com Contact etcconnect com contactETC 2020 ETC Trademark and patent info etcconnect com ip Product information and specifications subject to change ETC intends this document to be provided in its entirety 7490M2130 Rev E Released 2020 12 ...