ENGLISH
25
The analogue 4-20mA1 / 4-20mA2 outputs of the eSelect M follow the options previously selected Measurement Type i.e. pH o RX
pH
RX
Please note that the value displayed is automatically adjusted according to
the selected Measurement Type (see
SELECT MEASUREMENT TYPE PH
OR RX
menu)
The 4-20mA proportional analogue outputs are related to the measurements
in real time, in order to drive remote equipment such as data loggers, PLCs
or graphic recorders or other equipment suited to processing a remote mA
signal.
Select the value corresponding to 4 and 20 mA based on Setpoint 1.
Press E S C to go back to M E N U S E L E C T I O N or press E S C E S C to go back to M E A S U R E M E N T D I S P L A Y
A
4-20mA1 / 4-20mA2 OUTPUT pH or Rx > METERING FUNCTION ON SETPOINT
The analogue 4-20mA1 / 4-20mA2 outputs of eSelect M follow the options previously selected Measurement Type i.e. pH o RX
pH
RX
Please note that the value displayed is automatically adjusted according to
the Measurement Type selected (see
SELECT MEASUREMENT TYPE PH
OR RX
menu)
Select the Set point value to control the metering pump or other equipment
suited to processing the mA signal.
The mA setpoint is set (default) for
operations in ACID mode, the output
is active when the measured value is
higher than the selected setpoint, the
connected pump meters out an acid
The mA setpoint is set (default) for
operations in DIRECT mode: if the
measured value is lower than the
selected setpoint, the connected
pump meters out chlorine (Oxidising
Menu Selection
4-20mA (pH)
Menu Selection
4-20mA (RX)
SETTING 4-20mA (pH)
mA output mode
mA Device
mA Device
EXPERT MENU
SETTING 4-20mA (RX)
mA output mode
mA Device
EXPERT MENU
SETTING 4-20mA (pH)
Measurement
@4mA
0.00 pH
EXPERT MENU
SETTING 4-20mA (RX)
Measurement
@4mA
0 mV
EXPERT MENU
SETTING 4-20mA (pH)
Measurement
@20mA
14.00 pH
EXPERT MENU
SETTING 4-20mA (RX)
Measurement
@20mA
1000 mV
EXPERT MENU
Menu Selection
4-20mA (pH)
Menu Selection
4-20mA (RX)
SETTING 4-20mA (pH)
mA output mode
Setpoint
metering
EXPERT MENU
SETTING 4-20mA (RX)
mA output mode
Setpoint
metering
EXPERT MENU
SETTING 4-20mA (pH)
Setpoint Value
7.00 pH
EXPERT MENU
SETTING 4-20mA (RX)
Setpoint Value
200 mV
EXPERT MENU
SETTING 4-20mA (pH)
Metering
Acid
EXPERT MENU
SETTING 4-20mA (RX)
Metering
Direct
EXPERT MENU