Changing the access level
Checking outputs, changing terminal assignments
3
Checking outputs, changing terminal assignments
3.1
Changing the access level
Authorisation setting [Service]
The [Service] access level is required in order to adjust
certain parameters. To enable this, open the system
configuration
and tap the [Authorisation]
symbol. A settings window appears. Enter the
password "135" and press [Accept the authorisation] to
confirm.
3.2
Setting manual mode
Switching on an output manually
The terminal assignment of the individual components
of the selected function block are displayed in the
inputs and outputs menu, e.g. pumps, temperature
sensors, and mixers. In this menu, these can be
activated manually (manual mode), for example, to
check their function.
In the example below, the heating circuit pump of the
heating circuit is started manually.
The heating circuit pump is started manually
1. Increase the authorisation to [Service]. See
3.1 "Changing the access level"
.
2. Select the heating circuit and change the inputs
and outputs in the menu by tapping on the
symbol, followed by the
symbol. An overview
opens.
Fig. 3-1: Overview
3. In the heating circuit pump, tap on the
symbol.
A settings window appears. With the [On] button,
the pump is turned on manually, and turned off by
pressing the [Off] button.
Fig. 3-2: Settings window
4. If the pump is switched on manually, the [On]
button will light up yellow to confirm. In addition,
the name of the function block is displayed in red.
Fig. 3-3: Manual mode is activated
In manual mode, the [Automatic] button appears. It
is used to switch off manual mode, and automatic
mode is again started by the ETAtouch control
system. You can close this setting window with the
arrow on the left side, even if manual mode is still
active.
The ETAtouch control system automatically
reverts all manually switched on outputs back
to automatic mode after 30 minutes.
In the same manner, the running direction of a mixer is
checked. See the example below.