Overview of activities Maintenance
Empty the ash box
Empty the ash box
The control system issues reminders about
emptying the ash box after a set pellet
consumption.
The factory setting is 2,200 kg of pellets. If the ash
box is only partly full or overfilled, this value can
be changed. See page 13.
Stop heating,
draught fan switched off
Before emptying the ash box, switch off the boiler
in the overview with the
button. The boiler
performs a burnout.
Only when the draught fan is switched off and the
boiler status "Switched off" is displayed on the
screen is the burnout complete; then the ash box
can be removed.
Push up the front panel
The front panel stays in place in every position.
Ash box
Open the side latches
Open the side latches by pressing the safety catch
in the direction of the arrow. Pull the ash box
straight out from the front of the boiler.
Safety catch
Open latch
Empty the ash box; are there any embers?
Check the ash to see if there are any embers
present. Do not put hot ash in the waste bin due
to risk of fire.
Inspect the seals on the boiler.
Check the integrity of both seals. If the seals are
damaged, the boiler can draw in leak air. That
would reduce the boiler output.
Inspect seals
Attach ash box, restart heating
Reattach the ash box to the boiler and secure it
with the side latches.
In the "Boiler" overview, restart the boiler with the
on/off button
. The boiler automatically starts
heating if required.