• It should be replaced no later than 10 years after activation.
The battery is not replaceable.
6 • FUNCTION TABLE
No. Alarm signal
Red LED
Description
Solution
1
Intermittent
alarm signal.
Flashes at the same
time as the audible
alarm signal.
The detector's alarm is
triggered because smoke has
been detected.
If the alarm is triggered, it can be muted for 10 min.
by pressing the button briefly (max. 2 seconds).
2
Short signal
emitted every
35 seconds.
Two flashes
alternating with
the audible signal
every 35 seconds.
The alarm is muted for
10 minutes.
The alarm can be muted by removing the detector from
its base for 10 seconds or by using the test function:
press and hold the button for at least 3 seconds until a
loud, intermittent alarm signal can be heard.
3
No signal.
Flashes every 17
seconds.
The 24-hour alarm memory
will help you locate a triggered
detector.
The alarm memory can be deactivated by removing the
detector from its base for 10 seconds or using the test
function: press and hold the button for at least 3 seconds
until a loud, intermittent alarm signal can be heard.
4
Short signal
emitted every
35 seconds.
Two flashes
alternating with
the audible signal
every 35 seconds.
Fault signal indicating that the
battery is empty or there is a
malfunction.
The fault signal can be muted by removing the detector
from its base for 10 seconds or using the test function:
press and hold the button for at least 3 seconds until a
loud, intermittent alarm signal can be heard.
If the fault recurs, the detector must be replaced. If the
fault signal is triggered, the alarm can be muted for 12
hours by pressing the button briefly (max. 2 seconds).
5
No signal.
Two flashes every
35 seconds.
Detector fault signal muted for
12 hours.
The alarm can be muted by removing the detector
from its base for 10 seconds or by using the test
function:
press and hold the button for at least 3 seconds until a
loud, intermittent alarm signal can be heard.
ATTENTION: If the detector is exposed to excessive dust or water
over a prolonged period, this may trigger the alarm.
Summary of Contents for PROTECTOR K 10 PLUS
Page 2: ...2 ABB FIG 1 ABB FIG 2 ABB FIG 3 6 m 20 ABB FIG 4 ABB FIG 5 4 1 5 1 5 2...
Page 59: ...RU 59 2 20 50 60 15 6 4 3 5 1 4 1 5 1 35 5 2 5 2 3 4 5 2 10 2 10 35 12 2 3 3 10...
Page 60: ...60 RU 5 DIN EN 14604 1 DIN 14676 5 2 3 85 3 1 0 5 5 2 35 10 6 1 10 2...
Page 61: ...RU 61 2 35 35 10 10 3 3 17 24 10 3 4 35 35 10 3 12 2...
Page 62: ...62 RU 5 35 12 10 3 6 35 10 2...