DESCRIPTION OF APPLICATIONS

10. LIGHT CHANNEL FUNCTION

10.1 Switching

Threshold 0 = disabled, motion detection only
Threshold 1 – 2,000 lux (using the up/down menu) or directly enter a value 
between 0 and 2,000 lux
Default setting: 500 lux
There is an option of determining an offset (can also be assigned using 
objects 14 and 15) between “switching threshold ON/OFF 1” and “switching 
threshold ON/OFF 2”
-50% to +50%

Default setting: ±0%

Output telegrams can be sent in binary form (objects 8 and 9), as dim values 
(objects 12 and 13), (0-100%), or as scenes (objects 3/4 and 5/6), (1-64).
Individual parameters can be set for the switch ON and OFF values.

10.2 Controlling

• Dim value when controlling begins

Options: 0 - 100% (using the up/down menu) or direct entry 0 - 100%
Default setting: 60%

Control timing: Options: 0.5 - 10 seconds (up/down menu)

If the snooze function is enabled and presence is detected, the detector sends 
a value specified in the parameters instead of controlling/regulating the light.

  Note: If the control loop exhibits a hunting tendency, the sensor can be adjusted to 

various illuminants and ballasts using the “control timing” parameter.

As a rule of thumb: the slower the lighting responds, the longer the control timing (0.5-
10 seconds).

Summary of Contents for EP10427428

Page 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Page 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Page 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Page 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Page 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Page 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Page 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Page 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Page 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Page 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Page 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Page 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Page 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...

Reviews: