background image

GB

OPERATING INSTRUCTIONS

PD-C360i/8 KNX UP 

(EP10427404)

www.esylux.com 9/13

DESCRIPTION OF APPLICATIONS

10. LIGHT CHANNEL FUNCTION

10.1 Switching

Threshold 0 = disabled, motion detection only
Threshold 1 – 2,000 lux (using the up/down menu) or directly enter a value 
between 0 and 2,000 lux
Default setting: 500 lux
There is an option of determining an offset (can also be assigned using 
objects 14 and 15) between “switching threshold ON/OFF 1” and “switching 
threshold ON/OFF 2”
-50% to +50%

Default setting: ±0%

Output telegrams can be sent in binary form (objects 8 and 9), as dim values 
(objects 12 and 13), (0-100%), or as scenes (objects 3/4 and 5/6), (1-64).
Individual parameters can be set for the switch ON and OFF values.

10.2 Controlling

• Dim value when controlling begins

Options: 0 - 100% (using the up/down menu) or direct entry 0 - 100%
Default setting: 60%

Control timing: Options: 0.5 - 10 seconds (up/down menu)

If the snooze function is enabled and presence is detected, the detector sends 
a value specified in the parameters instead of controlling/regulating the light.

  Note: If the control loop exhibits a hunting tendency, the sensor can be adjusted to 

various illuminants and ballasts using the “control timing” parameter.

As a rule of thumb: the slower the lighting responds, the longer the control timing
(0.5-10 seconds).

Summary of Contents for EP10427404

Page 1: ...HAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately f 1 Hz LED display after warm up Each time motion is detected this is indicated by 2 flashes of the preset LED colour In the Master function the remote control entries will be acknowledged by 3 flashes from the blue LED In the Slave function...

Page 2: ...t 10 11 Output Light channel dimming length 4 bits Function constant light control regulation Telegrams can be transmitted to the dimming actuator via this object by manually pressing and holding down a touch sensor object 2 Only active when constant light control regulation has been enabled Object 12 Output Light channel dim value 1 length 1 byte Function constant light control regulation If arti...

Page 3: ...ngth 1 bit If persons are detected depending on the input delay an ON telegram is sent If no persons are detected depending on the switch off delay time an OFF telegram is sent Object 28 Output HVAC channel ON OFF length 1 bit If persons are detected depending on the input delay an ON telegram is sent If no persons are detected depending on the switch off delay time an OFF telegram is sent Object ...

Page 4: ...ject 45 Output Alarm ON OFF length 1 bit An alarm is triggered if a continuous number of movements are detected within a parametrisable time frame If Alarm must be acknowledged is not set in the parameters the alarm will be switched off if no movements are detected within a specific time frame Object 46 Output Sensor status length 1 bit Indicates whether the sensor head is assembled The types of t...

Page 5: ...REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enabled the connection with the lighting system is checked If the motion sensor detects movement the lighting will be ON for 5 seconds followed by a dead time of 1 second OFF The blue LED indicates that movement has been...

Page 6: ...reset time period Then several requests are sent to the sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion detection The LED will display the colour selected to indicate this 7 PRESENCE SIMULATION The detector keeps a constant record of if and when moveme...

Page 7: ... during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlling the lighting according to the preset target value If no more movement is detected the detector will revert to the previous automatic mode after the switch off delay time has elapsed Note Applies to all light chann...

Page 8: ...uator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light channel sends its current status in cycles according to specified time intervals At the same time it is also possible to determine whether it repeatedly sends OFF or ON telegrams in cycles 9 6 Behaviour at switching lock...

Page 9: ...ects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value when controlling begins Options 0 100 using the up down menu or direct entry 0 100 Default setting 60 Control timing Options 0 5 10 seconds up down menu If the snooze function is enabled and presence is detected the de...

Page 10: ...rthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication objects 14 and 15 If the maximal light value is reached a telegram is sent with a value of 0 If the lower light value is measured a telegram is sent with a value of 100 In between this the control variable is calculated on...

Page 11: ...hanges the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu in 5 steps Note only active for constant light control regulation Only active if orientation light has been set to ON Default setting 25 An OFF telegram via object 19 is used to switch off the orientation light func...

Page 12: ...f it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL Note the presence output is independent of the set light values Option of selecting input delay of 0 minutes or 2 minutes 30 minutes Default setting 0 minutes Option of selecting a switch off delay time of 0 1 60 min...

Page 13: ...lue An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value external light value x modifier x multiplier 13 3 Internal light value You can also check light control regulation by using objects 23 and 24 to output the internal light value directly from the sensor without factor o...

Reviews: