OPERATING INSTRUCTIONS

PD-C360i/8 KNX UP 

(EP10427404)

www.esylux.com 1/13

www.esylux.com

OPERATING INSTRUCTIONS

GB

Congratulations on your purchase of this high-quality ESYLUX product. To ensure correct device operation, 
please read these installation/operating instructions carefully and keep them in a safe place for future 
reference.

1 • SAFETY INSTRUCTIONS

 

WARNING! Work on electrical systems must be carried out by authorised personnel only, with 
due regard to the applicable installation regulations. Switch off the power supply before installing 
the system. Please observe the installation regulations laid out in the safety measure for 
separated extra-low voltage (SELV).

Use this product only as intended (as described in the user instructions). Do not make any 
changes or alterations as this will render any warrantees null and void. You should check the 
device for damage immediately after unpacking it. If there is any damage, you should not 
install the device under any circumstances.
If you suspect that safe operation of the device cannot be guaranteed, you should turn the 
device off immediately and make sure that it cannot be operated unintentionally.
For correct use of the device, ensure that the UC network (or KNX/EIB) to be connected is 
designed for protection class 3.

  NOTE: this device must not be disposed of as unsorted household waste. Used devices must be 

disposed of correctly. Contact your local town council for more information.

2 • 

DESCRIPTION

The ESYLUX PD-C360i/8 KNX UP is a presence detector with a 360° field of detection and 
integrated bus coupler for ceiling mounting. Follow the installation instructions provided 
when installing the device. The detector is able to control lighting ("switching" or "constant 
light control" features).
For additional features, please refer to the 

“Description of applications”

 section of the operating 

instructions. With a range of up to 8 m in diameter, the presence detector is suitable for use 
in offices, classrooms, conference facilities and halls with natural lighting.

The PD-C360i/8 KNX UP is intended to be used in a KNX (EIB), TP bus system in conjunction 
with other KNX components.

If the PD-C360i/8 KNX UP detects that persons are present in its field of detection, it 
transmits controlling telegrams for light outputs, depending on ambient brightness, and for 
HVAC (heating, ventilation and air conditioning) objects.

• Mixed light measurement is suitable for FL, PL, halogen and incandescent lamps.

Certified KNX/EIB training centres provide specialist training on how to plan, install, 
activate, document and use the ETS (Engineering Tool Software) that is required for 
parameter setting.

3 • INSTALLATION / ASSEMBLY / CONNECTION

 

See separate installation instructions.

Mobil-PDi/User

4 • START-UP

All parameter settings are carried out via the ETS 
(Engineering Tool Software). Pressing the programming 
button activates the programming status for the physical 
address on the PD-C360i/8 KNX UP. This is indicated by the 

blue LED

.

The product database and application description are 
available to download at www.esylux.com.

5 • SWITCH-ON BEHAVIOUR / LED DISPLAY

• Connect the bus supply

  This initiates a warm-up phase that lasts approx. 10 seconds.
 

The red LED

 and 

green LED

 will slowly flash alternately (f = 1 Hz).

• LED display after warm-up

  Each time motion is detected, this is indicated by 2 flashes of the 

preset LED colour

.

• In the “Master” function, the remote control entries will be acknowledged

 

by 3 flashes from the 

blue LED.

• 

In the “Slave” function

, each detection is acknowledged by 2 flashes of the 

green LED

.

 

NOTE: The green LED will only light up when motion is detected if it has been enabled by the ETS 
(Engineering Tool Software).

6 • TEST MODE

Parameters can be set via the ETS (Engineering Tool Software).
Test mode switches to the RUN status after “storing”, or 10 minutes after activating the test 
mode. The 

blue LED

 flashes to indicate movement.

7 • REMOTE CONTROL

The optional user remote control Mobil-PDi/User (EM10425547) can be used to regulate/
control the lighting.
The Mobil-PDi/User remote control adjusts the lighting value for the period that persons are 
present plus the switch-off delay time. Thereafter, the values set via the ETS (Engineering Tool 
Software) will apply.

 

NOTE: In the “Slave” function the detector does not respond to the remote control!

The Mobil-PDi/User can be used to control the lighting as follows:
• switching on or off
• dimming (only with “controlling” feature)
• storing and calling up of 2 scenes
• pressing the 

“Reset”

 

button resets the KNX presence detector to the 

values set via ETS (Engineering Tool Software). The stored light 
scenes 1 + 2 are kept.

For further information, please refer to the operating instructions for 
the Mobil-PDi/User remote control.

8 • ESYLUX MANUFACTURER

'S GUARANTEE

ESYLUX products are tested in accordance with applicable regulations and manufactured 
with the utmost care. The guarantor, ESYLUX Deutschland GmbH, Postfach 1840, D-22908 
Ahrensburg, Germany (for Germany) or the relevant ESYLUX distributor in your country (visit 
www.esylux.com for a complete overview) provides a guarantee against manufacturing/
material defects in ESYLUX devices for a period of three years from the date of manufacture.
This guarantee is independent of your legal rights with respect to the seller of the device.
The guarantee does not apply to natural wear and tear, changes/interference caused by 
environmental factors or damage in transit, nor to damage caused as a result of failure to 
follow the user or maintenance instructions and/or as a result of improper installation. Any 
illuminants or batteries supplied with the device are not covered by the guarantee.
The guarantee can only be honoured if the device is sent back with the invoice/receipt, 
unchanged, packed and with sufficient postage to the guarantor, along with a brief 
description of the fault, as soon as a defect has been identified.
If the guarantee claim proves justified, the guarantor will, within a reasonable period, either 
repair the device or replace it. The guarantee does not cover further claims; in particular, 
the guarantor will not be liable for damages resulting from the device's defectiveness. If the 
claim is unfounded (e.g. because the guarantee has expired or the fault is not covered by the 
guarantee), then the guarantor may attempt to repair the device for you for a fee, keeping 
costs to a minimum.

• 

PD-C360i/8 KNX UP

Summary of Contents for EP10427404

Page 1: ...HAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately f 1 Hz LED display after warm up Each time motion is detected this is indicated by 2 flashes of the preset LED colour In the Master function the remote control entries will be acknowledged by 3 flashes from the blue LED In the Slave function...

Page 2: ...t 10 11 Output Light channel dimming length 4 bits Function constant light control regulation Telegrams can be transmitted to the dimming actuator via this object by manually pressing and holding down a touch sensor object 2 Only active when constant light control regulation has been enabled Object 12 Output Light channel dim value 1 length 1 byte Function constant light control regulation If arti...

Page 3: ...ngth 1 bit If persons are detected depending on the input delay an ON telegram is sent If no persons are detected depending on the switch off delay time an OFF telegram is sent Object 28 Output HVAC channel ON OFF length 1 bit If persons are detected depending on the input delay an ON telegram is sent If no persons are detected depending on the switch off delay time an OFF telegram is sent Object ...

Page 4: ...ject 45 Output Alarm ON OFF length 1 bit An alarm is triggered if a continuous number of movements are detected within a parametrisable time frame If Alarm must be acknowledged is not set in the parameters the alarm will be switched off if no movements are detected within a specific time frame Object 46 Output Sensor status length 1 bit Indicates whether the sensor head is assembled The types of t...

Page 5: ...REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enabled the connection with the lighting system is checked If the motion sensor detects movement the lighting will be ON for 5 seconds followed by a dead time of 1 second OFF The blue LED indicates that movement has been...

Page 6: ...reset time period Then several requests are sent to the sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion detection The LED will display the colour selected to indicate this 7 PRESENCE SIMULATION The detector keeps a constant record of if and when moveme...

Page 7: ... during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlling the lighting according to the preset target value If no more movement is detected the detector will revert to the previous automatic mode after the switch off delay time has elapsed Note Applies to all light chann...

Page 8: ...uator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light channel sends its current status in cycles according to specified time intervals At the same time it is also possible to determine whether it repeatedly sends OFF or ON telegrams in cycles 9 6 Behaviour at switching lock...

Page 9: ...ects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value when controlling begins Options 0 100 using the up down menu or direct entry 0 100 Default setting 60 Control timing Options 0 5 10 seconds up down menu If the snooze function is enabled and presence is detected the de...

Page 10: ...rthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication objects 14 and 15 If the maximal light value is reached a telegram is sent with a value of 0 If the lower light value is measured a telegram is sent with a value of 100 In between this the control variable is calculated on...

Page 11: ...hanges the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu in 5 steps Note only active for constant light control regulation Only active if orientation light has been set to ON Default setting 25 An OFF telegram via object 19 is used to switch off the orientation light func...

Page 12: ...f it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL Note the presence output is independent of the set light values Option of selecting input delay of 0 minutes or 2 minutes 30 minutes Default setting 0 minutes Option of selecting a switch off delay time of 0 1 60 min...

Page 13: ...lue An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value external light value x modifier x multiplier 13 3 Internal light value You can also check light control regulation by using objects 23 and 24 to output the internal light value directly from the sensor without factor o...

Reviews: