EST SIGA-CRR Installation Sheet Download Page 3

 

Figure 3: Typical application 

AB4G

AB4G

+

+

(3)

(1)

(5)

(2)

(4)

 

(1)  Signaling line circuit (SLC) from previous device 
(2) SIGA-CR 

module 

(3)  Auxiliary riser in (24 VDC from regulated power supply listed for fire protective signaling) 
(4) SIGA-CRR 

module 

(5)  Riser monitor module or equivalent supervisory circuit 

 

Specifications 

 
Operating voltage 

15.20 to 19.95 VDC 

Current 
 Standby 
 Activated 

 
75 µA 
75 µA 

Ground fault impedance 

10 k

 

Contact rating (pilot duty) 

24 VDC at 2 A 

Circuit designation 
 

Signaling line circuit 

 
Class A, Style 6 or Class B, Style 4 

Compatible bases 

SIGA-AB4, SIGA-AB4G 

LPCB/CPD electrical box 

Requirements 
 
Minimum W × H × D 

 
Plastic box with cover plate, no 
gaps or unused holes 
2.4 × 3.5 × 1.5 in. (60 × 85 ×  
38 mm) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep single-gang 
box; 
4 in. square box, 1-1/2 in. (38 mm) 
deep, with single-gang cover 

Wire size 

12 to 18 AWG (0.75 to 2.5 mm²) 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93%, noncondensing 

Storage temperature range 

4 to 140°F (

20 to 60°C) 

 

Regulatory Information 

 
Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Authorized EU manufacturing representative:
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Year of manufacture 

The first two digits of the DATE MFG number 
(located on the product identification label) are 
the year of manufacture. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause 
harmful interference, and (2) this device must 
accept any interference received, including 
interference that may cause undesired 
operation. 

North American 
standards 

CAN/ULC-S527, UL 864 

European standards 

EN 54-18: 2005 Input/output devices 

P/N 387336P-EN • REV 6.0 • ISS 29FEB12 

 

3 / 4 

Summary of Contents for SIGA-CRR

Page 1: ...rnal appliances door closers fans dampers or equipment shutdown Table 1 Personality code listing information Code Description UL 864 CAN ULC S527 EN 54 18 8 Signal dry contact output Yes Yes Yes Installation Notes The module is shipped from the factory as an assembled unit it contains no user serviceable parts and should not be disassembled This module does not operate without electrical power As ...

Page 2: ...fications Each terminal on the module is limited to a single conductor To wire the module 1 Verify that all field wiring is free of opens shorts and ground faults 2 Make all wiring connections as shown in Figure 2 Figure 2 Wiring diagram 1 2 3 4 6 5 1 Auxiliary riser in from power limited regulated power supply listed for fire protective signaling 2 Auxiliary riser out to next sounder base Polarit...

Page 3: ...ang cover Wire size 12 to 18 AWG 0 75 to 2 5 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory Information Manufacturer Edwards A Division of UTC Fire Security Americas Corporation Inc 8985 Town Center Parkway Bradenton FL 34202 USA Authorized EU manufacturing representative UTC Fire Securit...

Page 4: ...l waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Contact information For contact information see www utcfireandsecurity com 4 4 P N 387336P EN REV 6 0 ISS 29FEB12 ...

Reviews: