  D A T A   S H E E T

 85001-0609

 

Not to be used for installation purposes.

  Issue 2  

Wiring

Single/Dual input Class A and Class B wiring (personality 5, 7, 19, 25, 27, 30) 
Ring tone for three-state and four-state telephone Class A and Class B wiring (personality 6, 26, 28, 29)

SIGA-CC2A

SIGA-MCC2A

Notes

  1 

For maximum wire resist-
ance and maximum wire 
distances, refer to IOMC 
Manual (P/N 270144).

  2 

Maximum #12 AWG 
(2.5mm

2

) wire. Min. #18 

(0.75mm

2

).

   
  3 

Refer to Signature Loop 
Controller Installation Sheet 
for wiring specifications.

  4 

These modules will NOT 
support two-wire smoke 
detectors.

  5 

All wiring power limited 
and supervised. If the input 
source is non-power limited, 
then maintain spacing of 
1/4 inch or use FPL, FPLP, 
FPLR or equivalent in accord-
ance with NEC.

  6 

The SIGA-UIO6 does not 
come with TB8 through 
TB13.

  7 

Supervised and power-
limited.

  8 

Supervised and power-
limited when connected to a 
power-limited source. If the 
source is nonpower-limited, 
maintain a space of 1/4 inch 
from power-limited wiring or 
use FPL, FPLP, FPLR, or 
an equivalent in accordance 
with the National Electrical 
Code.

  9 

The input for this riser is 
common to all modules.

Summary of Contents for SIGA-CC2A

Page 1: ...onality The actual operation of the module is determined by the person ality code selected by the installer It is downloaded to the module from the Signature loop controller during system configuration Standard Features Class A or B Operation Supports three and four state telephones Dual input riser select Use for connecting supervised 24 Vdc Audible Visible signal circuits or 25 and 70 VRMS Audio...

Page 2: ...perates as a riser selector for a four state open normal active trouble firefighter s telephone Only one telephone can be used with the CC2A at any given time When a telephone handset is plugged into its jack or lifted from its hook the module generates its own ring tone signal A separate ring tone riser is unnecessary The module sends this signal to the control panel to indicate the presence of a...

Page 3: ...dentifies each device on the loop and assigns a soft address to each serial number If desired the modules can be addressed using a laptop computer No addressing switches are used Warnings Cautions These modules do not provide supervision of the riser The fire alarm panel must provide this function These modules do not support conventional 2 wire smoke detec tors These modules will not operate with...

Page 4: ...ller Installation Sheet for wiring specifications 4 These modules will NOT support two wire smoke detectors 5 All wiring power limited and supervised If the input source is non power limited then maintain spacing of 1 4 inch or use FPL FPLP FPLR or equivalent in accord ance with NEC 6 The SIGA UIO6 does not come with TB8 through TB13 7 Supervised and power limited 8 Supervised and power limited wh...

Page 5: ...Voltage 20 VDC Current Standby 310 µA Alarm 135 µA Ground fault impedance 10 k Ohms Wire Size 12 to 18 AWG 2 5 to 0 75 sq mm Maximum line impedance Refer to the installation manual for your fire alarm control panel Output rat ings special applications 24 VDC 2 A 25 VAC audio 50 W 70 VAC audio 35 W EOL resistor value 47 kΩ Max circuit resistance Refer to manual Max circuit capacitance 0 1 µF Operat...

Page 6: ...329 F 866 503 3996 Canada Chubb Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T 65 6391 9300 F 65 6391 9306 India T 91 80 4344 2000 F 91 80 4344 2050 Australia T 61 3 9239 1200 F 61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity com 2010 UTC Fire Security All rights reserved ...

Reviews: