Page 4 of 6
D A T A S H E E T
85001-0609
Not to be used for installation purposes.
Issue 2
Wiring
Single/Dual input Class A and Class B wiring (personality 5, 7, 19, 25, 27, 30)
Ring tone for three-state and four-state telephone Class A and Class B wiring (personality 6, 26, 28, 29)
SIGA-CC2A
SIGA-MCC2A
Notes
1
For maximum wire resist-
ance and maximum wire
distances, refer to IOMC
Manual (P/N 270144).
2
Maximum #12 AWG
(2.5mm
2
) wire. Min. #18
(0.75mm
2
).
3
Refer to Signature Loop
Controller Installation Sheet
for wiring specifications.
4
These modules will NOT
support two-wire smoke
detectors.
5
All wiring power limited
and supervised. If the input
source is non-power limited,
then maintain spacing of
1/4 inch or use FPL, FPLP,
FPLR or equivalent in accord-
ance with NEC.
6
The SIGA-UIO6 does not
come with TB8 through
TB13.
7
Supervised and power-
limited.
8
Supervised and power-
limited when connected to a
power-limited source. If the
source is nonpower-limited,
maintain a space of 1/4 inch
from power-limited wiring or
use FPL, FPLP, FPLR, or
an equivalent in accordance
with the National Electrical
Code.
9
The input for this riser is
common to all modules.