P/N 3101773-
EN • REV 04 • ISS 05AUG13
•
When connecting the network data riser, always wire
the Network B (isolated) terminals on one SFS1-CPU
module to the Network A (nonisolated) terminals on
the next. See Figure
5
.
•
SLC wiring notes:
•
SLC wiring is supervised.
•
SLC2 (TB2) wiring is configured the same as SLC1
(TB1).
•
When connecting SLC wiring, if shielding is used it
must be continuous, terminated at the shield terminal,
taped throughout the entire circuit, and free from earth
ground.
•
SLC AUX power wiring is unsupervised.
•
SLC AUX power on loops 1 and 2 is nonisolated and
not used for loop smoke power.
•
SLC AUX power on loop 2 (TB2) is available whether
or not a second 3-SDC1 card is installed.
•
SLC smoke power (SMK PWR) on loop 2 (TB2) is not
available unless a second 3-SDC1 card is installed.
Figure 1: SFS1-CPU terminals and connectors
(1) SFS1-CPU front view
(2) SFS1-CPU back view
Table 1: SFS1-CPU terminals and connectors
Label
Description
Label
Description
J1
Not used
J15
Power supply cable connector
J2
RJ
-
45 Ethernet
cable connector
J17
Data ribbon cable connector
J3
Ethernet adapter card connector
J19
RJ
-11 telephone jack
J5
Not used
J21
Not used
J6 NETWORK
RS
-
485 network and fiber network
option card connector
TB1 LOOP CIRCUIT 1
Loop 1 signaling line circuit wiring
terminal
J7 LOOP CIRCUIT 2
Data circuit card connector for
signaling line circuit 2
TB2 LOOP CIRCUIT 2
Loop 2 signaling line circuit wiring
terminal
J8 LOOP CIRCUIT 1
Data circuit card connector for
signaling line circuit 1
TB4
Common relay wiring terminal
J9
LCD user interface connector
TB5
Network wiring terminal