General Description
MAGPRO-2i2O is an addressable input-output module. The module monitors 2 analogue input signals and
controls 2 relay outputs.
MAGPRO-2i2O
is powered on from the fire panel and can be controlled via the communication protocol.
The module is mounted is a separate small plastic box suitable for wall mounting.
Installation
Attention
:
Power off the loop circuit
before installing the MAGPRO-2i2O addressable module
!
1. Choose the proper place for installation of the
module. Undo the screws of the cover and open the box.
2. Set the module address using
MAGPRO-PROG programming tool
.
The address must be in the range from
1
to
250.
The set address is one for the entire module.
3. Dismount the module’s PCB from the box bottom. Mark the mounting holes on the installation surface. Drill
holes at the appropriate box side and run the cables to the module’s
loop and input-output terminals.
4. Mount the box bottom at the place of installation. Mount the PCB back on place.
5. Connect the cables to the loop and input-output terminals of the module according the shown Connection
diagrams.
6. Close the cover of the plastic box and fix it to the bottom with the supplied screws.
7. Test the module for proper operation and LED indication.
Installation Instructions
The MAGPRO-2i2O addressable module must be connected only to fire panels from MAGPRO Series!
!
Operating voltage
. . . . . . . . . . . . . . . . . . . . . 15÷32 VDC
Consumption stand-by mode . . . . . . . . . . . . 235
µА@27
VDC
Nom. current consumption . . . . . . . . . . . . . . 260
µА@27
VDC
O
utputs, electrical characteristics (max.) . . . DC 30V/1A; AC 125V/0.5A
Current consumption with 1 LED on . . . . . . .
3
.
5mA
Current consumption with
2
LEDs on . . . . . .
7mA
2
2
Installation wires
. . . . . . . . . . . . . . . . . . . . . . 0
.
4mm
÷
2.0mm
Relative humidity . . . . . . . . . . . . . . . . . . . . . .
≤
93% @ +40°C
Material (plastic) . . . . . . . . . . . . . . . . . . . . . . P
S
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gray
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN54-18
TECHNICAL SPECIFICATIONS
Distributor: Elite Security Products Ltd, Unit 7 Target Park, Shawbank Road Lakeside, Redditch B98 8YN, UK http://www.espuk.com
Manufacturer: Teletek Electronics JSC, 14 Srebarna Str., 1407 Sofia, Bulgaria, http://www.teletek-electronics.com
18020170; RevD; 03/2017
MAGPRO-2i2O
EN54-18
Dimensions
!
IP
40
-10°C
÷
+
6
0°C
Installation
!
~320
g
Indoor use
Outdoor use
1
293-CPD-0258
176mm
126mm
57mm
ATTENTION