General Description

MAGPRO-2i2O is an addressable input-output module. The module monitors 2 analogue input signals and 
controls 2 relay outputs.

  

MAGPRO-2i2O

 is powered on from the fire panel and can be controlled via the communication protocol.

The module is mounted is a separate small plastic box suitable for wall mounting.

Installation
Attention

Power off the loop circuit

 

before installing the MAGPRO-2i2O addressable module

!

1. Choose the proper place for installation of the

 

module. Undo the screws of the cover and open the box.

2. Set the module address using

 

MAGPRO-PROG programming tool

The address must be in the range from

 

to

 250.

 The set address is one for the entire module.

3. Dismount the module’s PCB from the box bottom. Mark the mounting holes on the installation surface. Drill 
holes at the appropriate box side and run the cables to the module’s

 

loop and input-output terminals. 

4. Mount the box bottom at the place of installation. Mount the PCB back on place. 
5. Connect the cables to the loop and input-output terminals of the module according the shown Connection 
diagrams.
6. Close the cover of the plastic box and fix it to the bottom with the supplied screws.
7. Test the module for proper operation and LED indication.

Installation Instructions

The MAGPRO-2i2O addressable module must be connected only to fire panels from MAGPRO Series!

!

Operating voltage

. . . . . . . . . . . . . . . . . . . . . 15÷32 VDC

Consumption stand-by mode . . . . . . . . . . . . 235

µА@27

VDC

Nom. current consumption . . . . . . . . . . . . . . 260

µА@27

VDC

O

utputs, electrical characteristics (max.) . . . DC 30V/1A; AC 125V/0.5A

Current consumption with 1 LED on . . . . . . .

3

.

5mA

Current consumption with 

2

 LEDs on . . . . . .

7mA

2

2

Installation wires

. . . . . . . . . . . . . . . . . . . . . . 0

.

4mm  

÷

 2.0mm

Relative humidity . . . . . . . . . . . . . . . . . . . . . .

93% @ +40°C

Material (plastic)  . . . . . . . . . . . . . . . . . . . . . . P

S

Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gray
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN54-18

TECHNICAL SPECIFICATIONS

Distributor: Elite Security Products Ltd, Unit 7 Target Park, Shawbank Road Lakeside, Redditch B98 8YN, UK http://www.espuk.com
Manufacturer: Teletek Electronics JSC, 14 Srebarna Str., 1407 Sofia, Bulgaria, http://www.teletek-electronics.com

18020170; RevD; 03/2017

MAGPRO-2i2O

EN54-18

Dimensions

!

IP

40

 -10°C 

÷

 +

6

0°C

Installation

!

~320

g

Indoor use

Outdoor use

1

293-CPD-0258

176mm

126mm

57mm

ATTENTION

Reviews: