26-1659-01
MCP DIL Switch Settings
The last device on the circuit must have its EOL signal enabled. Remove the cover as shown, then locate the
switch and set it to ‘ON’.
1)
2)
Technical Data
Dimensions
Width x Height .......................................87mm x 87mm
Flush / Surface Depth .............................25mm / 53mm
Operating Temperature
. ................................................................-10
o
C to +50
o
C
Voltage Ranges
DC Output from Mains Powered Panel ...25.5 to 35V DC
DC Output from Battery Powered Panel .20 to 26V DC
Operating Current (Typical) Quiescent ................................................50 uA
End of line ON if applicable .....................720 uA
(in addition to Quiescent)
Alarm Activated .......................................16.5 mA
LED Operation
Alarm Indication .......................................Pulsed twice per second
EOL indication .........................................5 second interval
Loading Units
Max Loading Units per zone ....................160 DLU
MAGDUO MCP. ...................................... 16.0 DLU
Flammability
.................................................................UL94-V2
IP Rating
.................................................................IP 21C
Part Code
.................................................................MAGDUOCP