26-1659-01 

 

MCP DIL Switch Settings 
 

The last device on the circuit must have its EOL signal enabled. Remove the cover as shown, then locate the 
switch and set it to ‘ON’.

  

 

1) 
 

 

 

2) 

 
 
 

Technical Data 
 

Dimensions  

Width x Height   .......................................87mm x 87mm 

 

Flush / Surface Depth  .............................25mm / 53mm 

Operating Temperature  

. ................................................................-10

o

C to +50

o

Voltage Ranges 

DC Output from Mains Powered Panel ...25.5 to 35V DC 

 

DC Output from Battery Powered Panel .20 to 26V DC 

Operating Current (Typical)  Quiescent ................................................50 uA 
 

End of line ON if applicable .....................720 uA  

 

(in addition to Quiescent) 

 

Alarm Activated .......................................16.5 mA 

LED Operation 

Alarm Indication .......................................Pulsed twice per second 

 

EOL indication .........................................5 second interval 

Loading Units 

 

 

 

Max Loading Units per zone ....................160 DLU 

 

MAGDUO MCP. ...................................... 16.0 DLU  

Flammability 

 .................................................................UL94-V2 

IP Rating 

 .................................................................IP 21C 

Part Code 

 .................................................................MAGDUOCP 

 
 

 
 

 