background image

Topology & Cabling  

All system wiring should be installed to comply with BS 5839: and BS 7671 (wiring regula ons) and any other standards 

relevant to the area or type of installa on. A cable complying with BS 5839: Pt 1: Category 1 (cables required to operate 

for prolonged periods during 

re condi ons) is required. This must be a 2-core 1.5mm2 screened 

re resistant cable (ie. 

FP200, Firetu

, Firecell, Lifeline or equivalent).  

The maximum total cable length from the control panel to a repeater is 500 metres.  

Up to 8 repeaters can be used but they must all be within the maximum 500 metres cable length.  

The cable 

screen must be connected to earth/ground at the control panel 

only.  

The cable 

screen continuity must be maintained 

at every point of the circuit, using the terminals provided or a suitable 

connec on block.  

Do not 

use a 4-core cable as a 24v supply and communica ons, due to the possibility of data corrup on. It is essen al 

that two 2-core screened cables are used, one for the 24V DC supply and the other for communica ons.  

Power Supply & Connections  

24V DC Power is provided from the control panel via Aux+ and Aux-.  

2-core 1.5mm2 screened 

re resistant cable 

When powering a repeater from the panel the extra current will reduce the ba ery backup run  me and has to be 

allowed for in the ba ery calcula ons.  

Current Drawn by Single Repeater @  24.0V DC 

 

Separate Power Supply Requirements 

 

The repeater can be powered by a separate 24v EN-54 power supply if required.  

The repeater working voltage range is between 21V DC to 32V DC with a maximum current of 50.0mA.  

Peripheral Bus Connections  

Communica ons between the panel and repeater is via a mul -drop RS-485 Peripheral Bus.  

2-core 1.5mm2 screened 

re resistant cable ((i.e. FP200, FP200, Firetu

, Firecell, Lifeline or equivalent) 

cable should be used for communica ons to the repeater and connected to the back board. 

The peripheral bus must be run from the panel to the 

rst repeater then the second repeater and so on; the peripheral 

bus must not be spurred from one point. 

26-1