MAGDUO Wall Sounders can be mixed on the same zone as other types of MAGDUO device. The above
diagram shows how to make the zone positive, zone negative and screen connections between the control
panel and MAGDUO Wall Sounder. Refer to the instruction leaflets supplied with other MAGDUO devices for
their equivalent wiring/terminal labelling details.
Please note that the E terminal on the MAGDUO Wall Sounder should only be connected to the zone cable
screen and NOT to the building earth. The cable screen is connected to earth at the panel end only, via the
zone “SCRN” terminal (or EARTH terminal on the MAGDUO panel). It is important to maintain the screen
continuity in order to protect against data corruption from interference.
Remember that the device at the end of the line must have its EOL signal activated using the
relevant DIL switch.
Do not use a resistor or capacitor (or another manufacturer’s End of Line
device) as the end of line, as this may prevent correct operation of the zone.
DIL Switch Settings
The detector DIL switches may be used to program the operation of
the
s
oun
der
. They may be altered whilst the device is still powered or
the system may be powered down completely.
The last device on the circuit must have the EOL signal enabled
(switch number 1 in the ‘ON’ position).
DIL SWITCH SETTINGS
1
2
3
4
End of line
Enabled
ON
Disabled
OFF
Sound Levels
High
ON
Low
OFF
Sound Patterns
Sound OFF
ON
ON
Dual Tone UK Evacuate
– 800 & 970 Hz
ON
OFF
Slow Whoop Up - 500 to 1200 Hz sweep up
OFF
OFF
Dual Tone French Warble
– 440 & 550 HZ
OFF
ON
S
W
IT
CH
OF
F
S
W
IT
CH
ON
1 2 3 4
O N
E