FIRE CONTROL PANEL

MAG816

INSTALLATION AND OPERATION 

MANUAL

READ THIS MANUAL BEFORE CONNECTING THE 

EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE.

To call our technical support line dial:

+44 (0) 1527 51 51 50

Summary of Contents for MAG816

Page 1: ...E CONTROL PANEL MAG816 INSTALLATION AND OPERATION MANUAL READ THIS MANUAL BEFORE CONNECTING THE EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE To call our technical support line dial 44 0 1527 51 51...

Page 2: ...4 Sounder Expander 12 Performance and Connecting of 4 Sounder Expander 12 4 CONNECTING 4 1 Relay Module MR8 13 4 2 Repeater Panel 15 4 3 Class Change Mode 16 4 4 Connecting the Zone and Sounder Circui...

Page 3: ...improper maintenance Damages resulting from any other cause bad maintenance or product misuse In the case of a reasonable number of unsuccessful attempts to repair the product covered by this guarant...

Page 4: ...consumption 200 at a normal mode Unlimited number of manual call points Thresholds for zone conditions 0 2 mA Open circuit fault condition 2 10 mA Normal condition 10 110 mA Fire alarm condition 110 m...

Page 5: ...2 General Technical Specifications of Relay Module MR8 Number of relays 8 Power supply 24V Current consumption in normal condition 8mA Additional current consumption for every relay switched ON 10mA M...

Page 6: ...g to be used see Position 9 from the spare parts kit on page 31 Perform an exposed or flushed mounting option see items 3 1 and 3 2 Run all external cables into the box to establish connection but do...

Page 7: ...ition 20 page 31 of the fire alarm panel on 25 mm thick drywall Use the dimension shown in Figure 6 to draw and cut out the mounting openings in the drywall Attach the hangers to the internal side of...

Page 8: ...ers and the bolts supporting the metal box 3 3 Configuration of the Basic Modules Figure 9 1 Metal clamp for supporting the battery 2 Clamp for supporting the main power supply cable 3 Terminal for co...

Page 9: ...resistors R 10K from the supplied spare parts kit position 1 page 31 to the sounder terminals DOUBLE Double Action Mode see item 5 2 MASTER Master Panel Mode see item 5 4 SLAvE Repeater Panel Mode se...

Page 10: ...t is possible that the battery might not be charged at the panel initial start up In this case the BATT LOW LOST at the control module and the GENERAL FAULT at the front panel will light on until the...

Page 11: ...tus indication Connecting of Additional 4 Zone Expander 1 Connect the connectors of the expanders 2 Fix the second 4 zone expander with screws from the spare parts kit position 10 page 31 to the metal...

Page 12: ...1 of the 4 sounder expander ZONE 2 to SOUNDER 2 and so on In case of fire in ZONE 1 SOUNDER 1 will operate continuously and Sounders 2 4 of the expander will be pulse activated 2 sec sound 2 sec sile...

Page 13: ...ormance of the MR8 Module Relays The MR8 Relays are activated upon an alarm event fire in the respective zone they are connected to If a sounder delay is set in the main control panel this delay will...

Page 14: ...nd Operation Manual Figure 17 Terminals and jumper configuration of MR8 Figure 18 Connecting between one Relay Module and Master Panel Figure19 Connecting between two Relay Modules and Master Panel Ma...

Page 15: ...10 Figure 20 shows the connection between the Master and Slave MAG816 panels Connecting of Repeater Panel When adding a repeater panel in the fire system Turn off the main and the stand by power supp...

Page 16: ...rs are also lit and the internal buzzer has been activated Disable the buzzer with the button on the front panel Check the mains fuse Check the electrical connections within the station box Check for...

Page 17: ...nt panel the problem lies with the connection of the circuits in these zones Check the polarity of the connection of the devices and whether there is a detector removed from its base Activate one or m...

Page 18: ...tion Check the polarity of the connection to the terminal of the main module of the panel as well as the connection to the 4 sounder expander 5 SySTEM PROGRAMMING 5 1 Sounder Delay This is an option f...

Page 19: ...ng time interval 2 two alarm signals are generated 5 3 Instant Action Mode Where in the armed site there are zones which need the sounders and the light indicators to be enabled instantaneously the pa...

Page 20: ...MR8 module relays is described in item 4 1 and the connection between the Master Panel and the Slave in item 4 2 5 5 Repeater Panel Mode In order to program the Repeater Panel mode Set a jumper on the...

Page 21: ...one expanders the LEDs of zones programmed in Instant Action mode i e with a set jumper light up in orange and all the rest in red On the 4 sounder expanders the Fault LED SND1 SND4 4 The following LE...

Page 22: ...Blinks at trouble in the sounder circuit OUTPUT DELAy yellow Lights permanently at programmed outputs time de lay a jumper is set on the TIME DELAY terminal ENABLE DISABLE yellow Lights permanently at...

Page 23: ...f ZONE 1 is enabled and lights permanently if ZONE 1 is disabled Press button until you reach the zone which has to be disabled The respective zone LED blinks in yellow 2 blinks per second Press butto...

Page 24: ...ou can exit the sounder disabling mode also by pressing the button as in that case the procedure for initial start up will not run To enable the sounders Press button DISABLE ENABLE LED blinks The ZON...

Page 25: ...e alarm Press button to continue with the system testing TEST LED will continue blinking The ZONE 1 LED lights out the zone is not longer in test mode The ZONE 2 LED blinks in yellow 2 blinks per seco...

Page 26: ...LT RP LED No connection with the Repeater panel Repeater fault GENERAL FAULT AUX LED Auxiliary supply fault GENERAL FAULT EARTH LED Short circuit to earth GENERAL FAULT uPFAULT LED Processor fault It...

Page 27: ...ti vated It is disabled by press ing the button FAULT A FAULT relay is activated The GENERAL FAULT yellow LED and the fault LED according to the Ta ble in item 7 1 light up simultaneously The internal...

Page 28: ...UMBERS Connection Diagram Expander 4 Zones Connection Diagram Expander 4 Sounders R 10K Thresholds for zone conditions 10 10 I 2 mA I 2 mA I 110 mA I 110 mA Open circuit fault condition Normal conditi...

Page 29: ...by Contract reference Service intervals Monthly Quarterly Half yearly Annually ZONE LOCATION DETECTOR TyPE and QUANTITy PER ZONE Ion Ph RoR F T CP 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TOTAL Ion Ion...

Page 30: ...Zones Tested Faults Rectified Signature of Engineer Next Due 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name FIRE AL...

Page 31: ...8 EOL module 2 9 Plastic cap 21 4 Zone Expander MAG816 Spare Parts Kit 10 Screw 3 6 DIN7985 4 11 Lightpipe for indication 1 12 EOL module 4 13 Jumper 1 4 Sounder Expander MAG816 Spare Parts Kit 14 Sc...

Page 32: ...18020607 Rev D 07 2013...