TECHNICAL SPECIFICATIONS 

Operating Voltage Range

9 - 

30

 VDC

 (Nom.12/24VDC)

Average c

urrent consumption

 in quiescent state . . . . . . .

< 5

0

µ

A

Alarm state current: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

 mA

 / 9V;

                                                                                           29mA / 12V; 
                                                                                           32mA/ 15V
Class (for the heat part, 

in accordance with EN54-5

/7) . . A1/R

Protected area (in accordance with EN54-5/7)

. . . . . . . .

up 120

Installation height

 

(in accordance with EN54-5/7)

. . . . . .

up 16m

Output in alarm state at terminal RI

. . . . . . . . . . . . . . . . .

20mA (max)/ -3.3V

(Towards terIN /+OUT/)

Degree of protection

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

IP30

2

2

Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . . . . . 0.4mm

 

ё

 2.0mm

 

Operational temperature range

. . . . . . . . . . . . . . . . . . . .

-1

0

C

 

ё

 +6

0

C

Relative humidity resistance

. . . . . . . . . . . . . . . . . . . . . .

(93

 ± 3)%

 @

 40

C

Dimensions (incl. base)

. . . . . . . . . . . . . . . . . . . . . . . . . .

ø102mm, h 48mm

Weight (incl. base)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

160g

. . . . . . . . . . . . . . . . . . . . . . . . .

°

°

°

1

293-CPD-0120

Distributor: Elite Security Products Ltd, Unit 7 Target Park, Shawbank Road
Lakeside, Redditch B98 8YN, UK http://www.espuk.com
Manufacturer: Teletek Electronics JSC, 14 Srebarna Str., 1407 Sofia, Bulgaria, http://www.teletek-electronics.com

CSD212

COMBINED SENSOR DETECTOR 

OPTICAL SMOKE AND RATE-OF-RISE

Installation Manual No: 18020743

ATTENTION:

 This manual is subject to change without  notice

!

 

Read carefully this installation instructions before installing the device!

GENERAL DESCRIPTION:

The 

CSD212

 is a special kit for using in intruder alarm systems. The kit includes the 

combined sensor fire detector 

CSD-2

 and relay base 

DB-12L/U 

(12V)

.

INSTALLATION
1. Choose the proper place for installation

 of the fire detector. Refer to the given 

installation instructions. 

Note:

 

Do not  install the detector near sources of steam, condensation or smoke 

and close to natural heat sources.

2. If you want to “lock” the detector to the base

 remove the little “tooth” (with the 

triangle shape) and break the plastic key off the base. Keep the plastic key in safe place 
to be able to open the detector later.

3.  Mount  the  relay  base

  on  the  ceiling  of  the  protected  premises  using  fixings

 

according the mounting surface.

4.  Connect the detector base

 to the intruder alarm  panel using the wiring diagram. 

ATTENTION: 

 Disconnect the main power supply  before installing the detector!

5. Insert the detector into the base 

and rotate clockwise until it drops into place. 

Continue to rotate the detector until it locks to the base  -  a click is heard.

6. If the detector has been locked

 

to the base,

 

when open it

 for a service schedule 

maintenance and cleaning you have to use the plastic key. Light press with the plastic 
key

 

into the base opening and at the same time rotate the detector head counter-

clockwise.

ATTENTION:

 To clean the wire mesh you have to remove the detector’s PCB and 

then carefully to disassemble the smoke chamber from it. Clean the wire mesh 
and mount the chamber back on the PCB as observe the arrows - they have to 
coincide, then slightly press the chamber to the detector’s PCB. Next you have 
to mount the PCB back to detector’s plastic body. Find the color dot sticker on 
the  PCB  and  orientate  it  to  the  mark  on  the  plastic  body  (visible  from  the 
outside). The hole next to the color dot have to coincide with the pin on the 
plastic body. Gently press downwards to fix the PCB in place.

TESTING THE DETECTOR
To test the detector use a smoke probe:

1.  Apply power to the detector.
2.  Wait  for 30 sec.
3. 

Exert influence on the fire detector by

 

smoke generator

 (

Dispenser)

 or by aerosol 

simulator of smoke to test the optical part; or use heat tester

 (Cordless Heat Detector 

Tester or Heat Tester 110V>240V)

 at

 

distance of 20 cm to test the heat part.

 Within 8 

sec the fire detector will enter in fire condition. Both LEDs will light up.
4. Power off the detector for 2 sec. minimum. After resetting the detector will enter in 
duty mode and the LEDs will light off.

SERVICE MAINTENANCE

1. Inspection for visible physical damage - weekly.
2. Operational test in real conditions - monthly.
3. Check and clean dust contamination - six months.
4. Check and clean base and head contacts and connections - annually.