EsiWelma Srl 

URD20SS_en.doc - rev. 0 

CO

2

 gas detectors – URD20SS 

24/09/2010 

Gas detection systems for industrial environments 

2/8

 

Technical 
characteristics 

 

Type of sensor 

NDIR (nondispersive infrared) 

Detectable Gas 

Carbon dioxide (CO

2

Power supply 

11÷28Vdc 

Max power consumption 

3.2W 

Measuring range  

0...20,000 ppm 

Precision 

±

 5% full scale, 

±

 10% readout 

Repeatability 

±

 5% full scale, 

±

 10% readout 

Measurement resolution 

20 ppm 

Microprocessor resolution 

1024 points (10 bit) 

Digital filter system 

Kalman Filter 

Watchdog Internal 
Warm-up time 

< 2m 

Stabilization time 

< 2m 

Response time 

< 25s (T90) 

Average Sensor life (in air) 

255 weeks 

4..20mA Output 

Proportional mode 
(default) 

 

Consumption mode 
(applications at 1 or 2 
thresholds) 
 

 

4…20mA Output reference 
selection: 

 
-   4mA   = 0 ppm 
- 20mA   = 20000 ppm 

 

-   0mA   = no alarm 
- 10mA   = 1

st

  threshold alarm 

- 20mA   = 2

nd

  threshold alarm 

 

 
 
by jumper selectable polarity 

4…20mA output load resistor 

- up to 200

 at 12Vdc power supply 

- 200

 

÷

 700

 at 24Vdc power supply 

Operating Temperature 
Storage Temperature

 

-20 

÷

 50 °C 

-20 

÷

 70 °C

 

Relative Humidity 

(without condensing)

Operation 

Storage 

 

 

15 

÷

 90 %RH 

45 

÷

 75 %RH

 

Operating pressure (KPa) 

80 

÷

 110 

Air speed (m/s) 

 6 

Visual warnings 

Red LED visible with detector energised 

Dimensions and weight 

See dedicated section 

Options & Accessories 

 

Card with 4 SPDT relays 

UZR20.4

 

NO or NC contacts available, 
jumper selectable 

See threshold limit settings

  

 

Maximum relay capacity: 

50mA at 24Vac/dc, 100mA at 12Vac/dc 

  

direct: relay ON when an event is 
detected 

reverse: relay ON when no event is 
detected 

TUL40..

 Gas calibration kit 

See installation and commissioning chapter

 

TUS40   

Handheld terminal   

for service and maintenance  

See installation and commissioning chapter 

CRG40

   Gas collecting cone 

See dedicated data sheet 

PAP40

   Powerful jets protection 

See dedicated data sheet 

 

 
ATEX markings 

 

       

 

 

II 3G  Ex nA nC d IIC T6 

 

 BVI 07 ATEX 0033 

 

-20°C 

 T

A

 

 +50°C

 

Summary of Contents for Sensigas URD20SS

Page 1: ...etects carbon dioxide leaks or emissions in industrial environments hospitals fermentation plants greenhouses stables and more in general where carbon dioxide is stored generated or produced URD20SS sensors can be used in stand alone mode with 4 20mA output or with an optional voltage free contact relay card having the following four digital outputs Pre alarm 1st alarm threshold 2nd alarm threshol...

Page 2: ...larm by jumper selectable polarity 4 20mA output load resistor up to 200Ω at 12Vdc power supply 200Ω 700Ω at 24Vdc power supply Operating Temperature Storage Temperature 20 50 C 20 70 C Relative Humidity without condensing Operation Storage 15 90 RH 45 75 RH Operating pressure KPa 80 110 Air speed m s 6 Visual warnings Red LED visible with detector energised Dimensions and weight See dedicated sec...

Page 3: ...s that of air so it tends to collect at floor level in closed unventilated environments Therefore the sensor must be installed about 30 cm above the floor level Take into consideration the following specific installation guidelines as well as the above instructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from h...

Page 4: ...be made by JP2 triple of jumpers to change this setting operator has to move JP2 jumpers as shown in the figure Caution if the default settings are changed the connections on the TB1 terminal board will be inverted Ref at default Ref at To set the operating mode of the 4 20mA signal it is necessary to use the 5th selector of the DIP switch at S1 in particular Proportional Threshold mode To set the...

Page 5: ...s below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot flexible tab Step 2 Fit the relay card snugly and pull the flexible tab of the connection slot towards the main terminal terminal board Flexible tab Step 3 Check the position of the card Make su...

Page 6: ...al installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will enter a 2 minute warm up phase after power up After this time the sensor will switch to normal operating mode but it will take about 2 hours before it reaches top performance level When ...

Page 7: ...to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 gas calibration kit and the TUS40 handheld terminal which must be connected to the sensor via the communication interface integrated in the cable on the connector CN4 For the re calibration procedure see the instructions supplied with the handheld terminal Remove power f...

Page 8: ...use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mist Ex nA nC d IIC T6 Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type examination certificate 20 C TA 50 C Operating temperature range Installation data To be filled in by Installer Installer s stamp and signature I...

Reviews: